6.4.4 Chimneys already in use
If a chimney used before for oil or solid fuel-fired boilers is used as a duct
for installation of a concentric exhaust gas pipeline, the chimney must be
thoroughly cleaned first by a specialist.
Note
Concentric flue gas routing, also in the duct, also in the shaft, is
absolutely necessary The concentric flue gas pipe must run
straight in the duct.
Multiple usage of air/flue gas chimneys of different manufactur
ers
The selected air/flue gas chimney must have approval by the
building supervisory authority DIBt for multiple usage opera
tion suitability.
Diameter, heights and maximum number of devices can be
taken from the design tables of the approval certificate.
Height above the roof
With regard to the minimum height above the roof, country-
specific regulations regarding chimneys and flue gas systems
are applicable.
6.4.5 Assembly of the flue gas system
Warning
Danger of injury by not wearing working gloves.
Working gloves must be worn during assembly of the flue gas sys
tem.
Mounting with gradient
The flue pipe must be routed at a gradient to the EC four so that the con
densation from the flue pipe can drain from the flue pipe to the central con
densation collector of the EC four.
The min. downward slopes are:
horizontal flue pipe: min. 3° (min. 5.5 cm per metre)
external wall duct: min. 1° (min. 2.0 cm per metre)
Shortening of the pipes
All simple and concentric pipes may be shortened. After cutting, the ends
of the pipes have to be thoroughly de-burred. When a concentric pipe is
shortened, a piece of pipe at least 6 cm long must be cut off the outer
pipe. The spring washer for centring the inner pipe becomes obsolete.
Minimum dimensions of the duct
Outer Ø cou
pling
Min. duct inner dimension
System
D
[mm]
short side A
[mm]
round B
[mm]
SAS 160 (DN 160)
184
225
245
SAS 200 (DN 200)
227
256
276
Back ventilation
For room air-depending operation of the gas condensing boiler with the
SAS 160 and SAS 200 the duct below the flue gas connection in the in
stallation room must be provided with back ventilation. The clear cross-
section must be at least A
min
= 125 cm
2
. A respective air intake grid is
available as accessory.
Fig.24 Minimum dimensions of the duct
RA-0000159
6 Installation
7636047 - 02 - 24082015
47
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...