9.2.13 Solar
Temp diff on (3810) and Temp diff off (3811)
1 / 0 On / off collector pump
T Temperature
T1 Temp diff on
T0 Temp diff off
TK Collector temperature
TL Charging temperature min buffer storage tank / swimming pool
TS Storage tank temperature
t Time
The switching-on and switching-off point of the collector pump is set with
these functions. Basis is the temperature difference between collector
temperature and storage temperature.
Charg temp min HW st tank (3812)
In addition to the temperature difference, reaching a certain minimum col
lector temperature is necessary for the storage charging process.
Temp diff on buffer (3813),Temp diff off buffer (3814)
andCharging temp min buffer (3815)
The switching-on and switching-off point of the collector pump is set with
these functions. Basis is the temperature difference between collector
temperature and storage temperature of the buffer storage tank.
In addition to the temperature difference, reaching a certain minimum col
lector temperature is necessary for the buffer storage charging process.
Temp diff on swi pool (3816) andTemp diff off swi pool (3817)
The solar circuit pump starts or stops if the difference between the solar
collector temperature and the swimming pool temperature is exceeded or
undershot.
Charging temp min swi pool (3818)
Temperatures that the collector must have at the least in order to begin
charging a swimming pool.
Charging prio storage tank (3822)
If several heat exchangers/indirect coils are tied into the system, the heat
ing sequence for the connected cylinders can be determined by setting the
heating process.
None: Every storage tank is charged alternately with a temperature in
crease of 5 °C, until the setpoint has reached level A, B or C (tab. 1).
Once all setpoints have been reached, the setpoints of the next level are
applied.
Hot water storage tank: The DHW storage tank is charged as priority
during any heating with solar energy at any level (A, B or C). Other con
sumers with the same level will only be charged afterwards. Once all
setpoints have been reached, the setpoints of the next level are applied.
For this, heating the DHW cylinder still takes priority.
Buffer storage tank: During any heating with solar energy, the buffer
storage tank is charged first at any level (A, B or C). Other consumers
with the same level will only be charged afterwards. Once all setpoints
have been reached, the setpoints of the next level are applied. For this,
charging the buffer cylinder still takes priority.
Tab.10 Storage tank setpoints
Lev
el
Domestic water stor
age tank
Buffer storage tank
Swimming pool
(1)
A
Nominal value
(prog. no. 1610)
Buffer setpoint
(drag-pointer)
Setpoint solar heat
ing
(prog. no. 2055)
Fig.39 Charging control /schematic)
TK
T1
T2
TL
1
0
TS
RA-0000080
T
t
9 Settings
7636047 - 02 - 24082015
101
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...