40 for buildings with thick walls or outer insulation.
20 for buildings of normal building design.
10 for buildings of light building design.
Central setp compensation (6117)
The central setpoint lead monitors the heat generator setpoint to the re
quired central flow temperature. With the setting the maximum corrector is
restricted, even if a larger adaptation should be required.
System frost protection (6120)
The heating circuit pump is activated without heat request subject to out
side temperature. If the outside temperature reaches the lower limit value
of -4°C, the heating circuit pump is activated. The pump is activated every
6 hours for 10 minutes when the outside temperature is between -5°C and
+1.5°C. When the upper limit value of 1.5°C is reached, the pump
switches off.
Save sensors (6200)
Sensor modes can be saved under prog. no. 6200. This is done automati
cally; however, after change of the heating system (removal of a sensor)
the state must be saved again to the sensor terminals.
Reset to default parameters (6205)
The factory setting of the regulator is written to the regulator.
Caution
The regulator parameters are overwritten. The factory settings are
stored in the regulator.
Activation of prog. no. 6205:
The regulator is reset to factory setting.
Check no. heat source 1 (6212), Check no. heat source 2
(6213), Check no. storage tank (6215) and (6217)Check no.
heating circuits
The standard device generates a check number to identify the system
scheme; this comprises the numbers listed in the table below.
Tab.11 Check no. heat source 1 (prog.-no. 6212)
Solar
A collector field
with sensor B6
and collector pump
Q5
Tank charging
pump for
buffer storage tank
K8
Solar diverting
valve for
buffer storage tank
K8
Solar charging
pump for
swimming pool K18
Solar diverting
valve for
swimming pool K18
External solar ex
changer, Solar
pump K9
DHW=DHW stor
age tank
B=Buffer storage
tank
0
No solar
1
*
3
DHW/B
5
X
6
X
8
X
DHW+B
9
X
DHW/B
10
X
DHW
11
X
DHW
12
X
P
13
X
P
14
X
15
X
9 Settings
114
7636047 - 02 - 24082015
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...