6.4.2 Flue gas system
Fig.23 EC four with flue gas piping system SAS for room air-dependent and room air-independent operation
C
33
C
33
C
83
B
23
B
23P
C
53
C
53
rear ventilation
air inlet
50 cm
2
- 450 cm
2
depending on boiler output
air inlet
1 x 150 cm
2
or
1 x 75 cm
2
air inlet
50 cm
2
- 450 cm
2
depending on boler
output
air inlet
1 x 150 cm
2
or
1 x 75 cm
2
air inlet
1 x 150 cm
2
or
1 x 75 cm
2
air inlet
1 x 150 cm
2
or
1 x 75 cm
2
rear ventilation
wall connection set
WAS
RA-0000415
In case of roof central heating installations, the installation of the roof
duct is only possible if the flue gas pipe can be routed directly (without
going through other rooms) through the roof.
In case of installation C
33
(suction of the combustion air through vertical
roof duct) the mouth of the air pipe must be fitted with a rain hood.
In case of installation C
53
and C
83
(suction of the combustion air through
the outer wall) the wall connection kit WAS with filter mat and air pres
sure monitors must be used.
Flue gas pipeline lengths for room air-dependent operation
Tab.7
Permissible exhaust gas pipeline lengths for room air-dependent operation
Model
EC four
125 kW
EC four
170 kW
EC four
215 kW
EC four
260 kW
EC four
300 kW
Flue gas pipe-Ø
mm
160
160
160
200
160
200
160
200
Max. pipe length incl. 1
elbow 87°
m
60
50
30
60
18
60
8
60
These lengths only apply to single boilers.
For more elbows, the following deductions have to be made
1 elbow 87°: 5 m
1 elbow 45°: 2 m
1 elbow 15°: 1 m
A calculation by Potterton is required for individual cases of room air-inde
pendent operation of the EC four.
6 Installation
7636047 - 02 - 24082015
45
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...