Model
EC four
125 kW
EC four
170 kW
EC four
215 kW
EC four
260 kW
EC four
300 kW
Natural gas
80/60°C kW
19.2-121.6
26.8-165.8
33.5-210.1
40.2-254.5
45.9-294.3
50/30°C kW
21.3-133.1
29.8-181.3
37.4-229.6
44.9-278.1
52.3-322.1
LPG
80/60°C kW
33.5-121.6
33.5-165.8
46.0-210.1
55.5-254.5
55.9-294.3
50/30°C kW
37.2-133.1
37.3-181.3
51.2-229.6
62.0-278.1
63.2-322.1
Standard utilisation (Hi/Hs)
75/60°C %
106.5/95.5
106.6/95.6
106.6/95.6
106.7/95.7
106.7/95.7
40/30°C %
109.5/98.5
109.6/98.6
109.6/98.6
109.7/98.7
109.7/98.7
Data for design of the chimney to DIN EN 13384 (room air-dependant operation)
Flue gas temperature
80/60°C °C
57-61
57-61
57-60
57-61
56-60
50/30°C °C
30-37
30-37
30-37
30-38
30-37
Flue gas mass flow rate
with natural gas
80/60°C g/s
9.1-56.8
12.7-77.2
15.9-97.6
19.1-118.1
21.8-136.2
50/30°C g/s
8.2-52.3
11.5-71.1
14.4-89.4
17.4-108.3
19.7-124.5
For liquid gas
80/60°C g/s
15.1-53.9
15.1-73.2
20.7-92.6
25.0-112.0
25.0-129.2
50/30°C g/s
14.2-49.4
13.9-67.1
19.2-84.4
23.3-102.2
22.9-117.6
NOx standard emission factor
75/60°C mg/kWh
35
CO standard emission factor
50/30°C mg/kWh
15
Supply pressure for natural gas
min. 18 mbar - max. 25 mbar
CO
2
content natural gas
%
9.3 (9.1-9.5 allowed)
Supply pressure LPG
min.42.5 mbar - max. 57.5 mbar
CO
2
content LPG
%
11.0 (10.8-11.2 allowed)
pH value condensed water before
neutralisation
4-5
Volume condensed water
40/30°C l/h
3.0-16.6
4.3-22.6
5.4-29.9
6.0-36.5
7.6-42.4
Max. delivery pressure at flue gas outlet
mbar
1.0
Flue gas connection
mm
160
200
Connection values
IP rating
IP 20
Electrical connection
230 V~ / 50Hz, max. 6.3 A
Max. electr. power consumption
W
170
200
330
350
410
EnEV-values
%
0.24
0.22
0.20
0.18
0.16
Standby losses q
B
, 70
%
0.24
0.22
0.20
0.18
0.16
Efficiency η
100
%
97.3
97.5
97.7
97.9
98.1
Efficiency η
100
%
108.8
108.8
108.9
109.0
109.0
Demand on auxiliary energy P
HE
,
100
170
200
330
350
410
Demand on auxiliary energy P
HE
,
100
31
34
40
46
51
Max. water pressure
6.0 bar / 0.6 MPa
Max. operating temperature (protection)
°C
110
Max. flow temp
°C
90
Volume flow
∆T = 20 K
kg/h
5375
7310
9245
11180
12900
∆T = 10 K
kg/h
10750
14620
18490
22360
25800
Hydraulic resistance
∆T = 20 K
mbar
28
34
37
39
40
3 Technical specifications
14
7636047 - 02 - 24082015
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...