Burner control
Prog. no.
Level
Standard value
Required output prepurging
(1)
9504
E
EC four 125 kW: 73
kW
EC four 170 kW: 94
kW
EC four 215 kW: 96
kW
EC four 260 kW: 120
kW
EC four 300 kW: 129
kW
Required output ignition
1)
9512
E
EC four 125 kW:
59.3 kW
EC four 170 kW:
75.5 kW
EC four 215 kW:
77.1 kW
EC four 260 kW:
97.7 kW
EC four 300 kW:
103.9 kW
Required output LF
1)
9524
E
EC four 125 kW: 20
kW
EC four 170 kW: 28
kW
EC four 215 kW: 35
kW
EC four 260 kW: 42
kW
EC four 300 kW: 48
kW
Required output HF
1)
9529
E
EC four 125 kW: 125
kW
EC four 170 kW: 170
kW
EC four 215 kW: 215
kW
EC four 260 kW: 260
kW
EC four 300 kW: 300
kW
Postpurge time
9540
E
20 s
Fan output/speed slope
9626
E
EC four 125 kW:
37.1
EC four 170 kW:
27.6
EC four 215 kW:
26.4
EC four 260 kW:
20.1
EC four 300 kW:
19.9