Fault
code
Fault description
Explanations/causes
110
Safety temperature limiter lockout
No heat removal, STB interruption, possible short-circuit in the
gas valve
(2)
, internal fuse faulty; allow device to cool down and
carry out reset; if the fault occurs several times inform the in
staller
(3)
111
Temperature monitor switching off
No heat supply; pump defect, radiator valves closed
1)
119
Fault pressure switch
Check water pressure and top up with water if necessary
1)
121
Flow temperature 1 (Heating circuit 1) monitoring
122
Flow temperature 2 (Heating circuit 2) monitoring
126
DHW charging monitoring
127
Legionnaire's disease germs temperature not
reached
128
Flame failure during operation
132
Gas pressure monitor or air pressure monitor fault
Lack of gas, contact GW opened, external temperature moni
tor
133
No flame during the safety time
Reset, if the fault re-occurs several times contact installer,
lack of gas, polarity of mains connection, safety period, check
ignition electrode and ionization current
1)
3)
146
Configuration fault common message
151
Internal fault
Check parameters (see adjustment table installer and/or call-
up values), unlock LMS, replace LMS, installer
1)
3)
152
Parameterization fault
160
Fan fault
Fan possibly defective, speed threshold set wrongly
3)
162
Air pressure monitor does not close.
171
Alarm contact H1 or H4 activated
172
Alarm contact H2 (EM1, EM2 or EM3) or H5 activated
178
Temperature monitor heating circuit 1
179
Temperature monitor heating circuit 2
183
The device is in parameter setting mode
217
Sensor fault
218
Pressure monitoring
241
Flow sensor solar sensor fault
242
Return sensor solar sensor fault
243
Swimming pool sensor fault
260
Flow temperature 3 sensor fault
270
Monitoring function
317
Mains frequency outside of valid range
320
DHW charging temp sensor fault
322
Water pressure too high
Check water pressure and drain water if necessary
1)
323
Water pressure too low
Check water pressure and top up with water if necessary
1)
324
BX same sensors
325
BX / extension module same sensors
326
BX / mixer group same sensors
327
Extension module same function
328
Mixer group same function
329
Extension module / mixer group same function
330
Sensor BX1 no function
331
Sensor BX2 no function
11 Troubleshooting
7636047 - 02 - 24082015
139
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...