Note
If you change this value, please note that prog.no. 2452
(Controller delay fan output) is always higher.
Required output HF (9529)
Nominal output fan speed under boiler in HF
Postpurge time (9540)
After-venting time.
Caution
This parameter must only be changed by a heating specialist!
Fan output/speed slope (9626) and Fan output/speed Y-
section (9627)
The speed of the fan can be adjusted with this. This is important for com
plex installations or change to LPG.
Prog 9626 corresponds to the slope of the fan curve
Prog 9627 corresponds to the displacement of the fan curve in Y-direc
tion
9.2.26 Info option
Different information values are displayed depending on the operating
conditions. In addition, information about the status is displayed.
9 Settings
7636047 - 02 - 24082015
129