Product name
EC four
125 kW
EC four
170 kW
EC four
215 kW
EC four
260 kW
EC four
300 kW
Low-temperature boiler
(1)
No
No
No
No
No
B1 boiler
No
No
No
No
No
Cogeneration space heater
No
No
No
No
No
Combination heater
No
No
No
No
No
Rated heat output
Prated
kW
122
166
210
255
294
Useful heat output at rated heat out
put and high temperature mode
(2)
P
4
kW
121.6
165.8
210.1
254.5
294.0
Useful heat output at 30% of rated
heat output and low temperature
mode
(1)
P
1
kW
40.5
55.2
69.7
84.4
97.3
Seasonal space heating energy effi
ciency
ƞ
s
%
–
–
–
–
–
Useful efficiency at rated heat output
and high temperature mode
(2)
ƞ
4
%
87.7
87.8
88.0
88.2
88.3
Useful heat output at 30% of rated
heat output and low temperature
mode
(1)
ƞ
1
%
97.4
97.5
97.4
97.5
97.4
Auxiliary electricity consumption
Full load
elmax
kW
0.170
0.200
0.330
0.350
0.410
Part load
elmin
kW
0.031
0.034
0.040
0.046
0.051
Standby mode
P
SB
kW
0.004
0.004
0.004
0.004
0.004
Other items
Standby heat loss
P
stby
kW
0.180
0.224
0.258
0.281
0.288
Ignition burner power consumption
P
ign
kW
0.0
0.0
0.0
0.0
0.0
Annual energy consumption
Q
HE
GJ
–
–
–
–
–
Sound power level, indoors
L
WA
dB
66
67
67
67
68
Emissions of nitrogen oxides
NO
X
mg/kW
h
38
38
39
39
39
(1) Low temperature mode means for condensing boilers 30 °C, for low temperature boilers 37 °C and for other heaters 50 °C return tem
perature (at heater inlet).
(2) High temperature mode means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
See
The back cover for contact details.
3.2.2 Technical data
Model
EC four
125 kW
EC four
170 kW
EC four
215 kW
EC four
260 kW
EC four
300 kW
Product ID no.
CE-0085 CL 0072
VDE Reg. No.
40017550
Gas category
II
2H3+
Installation types
B
23
, C
33
, C
53
, C
63X
, C
83
Software version
V 4.2
Nominal heat input range
Natural gas
Heating kW
20.0-125.0
28.0-170.0
35.0-215.0
42.0-260.0
48.0-300.0
LPG
Heating kW
35.0-125.0
35.0-170.0
48.0-215.0
58.0-260.0
58.0-300.0
Nominal heat output range
3 Technical specifications
7636047 - 02 - 24082015
13
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...