B
Charging temp max
(prog. no. 5050)
Charging temp max
(prog. no. 4750)
Setpoint solar heat
ing
(prog. no. 2055)
C
Storage tank temp
max
(prog. no. 5051)
Storage tank temp
max
(prog. no. 4751)
Swimming pool temp
max
(prog. no. 2070)
(1) With swimming pool heating set as priority (prog. no. 2065), the swimming
pool will be heated before the storage tanks.
Charging time relative prio (3825)
If the preferred storage tank corresponding to the charging control not be
charged, during the time set here the priority goes to the next storage tank
or the swimming pool.
Waiting time relative prio (3826)
Transfer of priority is delayed by the time selected here.
Waiting time parallel op (3827)
Parallel operation is feasible when using solar primary pumps subject to
there being sufficient solar energy available. For this, in addition to the
storage tank currently being heated, the next storage tank in the priority
order can also be heated in parallel. The storage tank switching on for par
allel operation can be delayed and stepped by the value set here.
Delay secondary pump (3828)
Operation of the secondary pump of the heat exchanger/indirect coil can
be delayed to enable any cold water that may be present to be flushed
through the primary circuit first by the pump.
Collector start function (3830)
If the temperature at the collector with the pump turned off is not meas
ured correctly (e.g. with vacuum tubes), then a periodic switching on of the
pump is possible.
Caution
The temperatures at certain collectors cannot be measured cor
rectly if the pump is switched off. For this reason, the pump must
be activated from time to time.
Min run time collector pump (3831)
The collector pump is periodically switched on for the running time set
here.
Collector start function on (3832) and Collector start function
off (3833)
The time when the collector start function starts or stops is set here.
Collector start funct grad (3834)
As soon as there is a temperature increase on the collector sensor, the
collector pump switches on. The higher the value selected here, the great
er the temperature rise must be.
Collector frost protection (3840)
In order to prevent freezing of the collector, the collector pump will be acti
vated in case of frost danger.
Collector overtemp prot (3850)
In case of overheating danger, charging of the storage tank is continued in
order to remove heat. When the storage tank safety temperature has been
reached, charging of the storage tank will be interrupted.
Evaporation heat carrier (3860)
Pump protecting function, to prevent overheating of the collector pump in
case of evaporating danger of the heat carrying medium due to high col
lector temperature.
9 Settings
102
7636047 - 02 - 24082015
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...