Time program heating circuit 5
Prog. no.
Level Standard value
Copy?
615
Eu
Default values
No | Yes
616
Eu
No
Holidays heating circuit
1
Prog. no.
2
(1)
Prog. no.
3
(1)
Prog. no.
Level Standard value
Select
Period 1 | Period 2 | Period 3 | Period 4 | Period 5 |
Period 6 | Period 7 | Period 8
641
651
661
Eu
Period 1
Start
642
652
662
Eu
—.— (day.month)
End
643
653
663
Eu
—.— (day.month)
Operating level
Off | Reduced
648
658
668
Eu
Off
(1) Parameters only visible if heating circuit is installed.
Heating circuit
1
Prog. no.
2
(1)
Prog. no.
3
(1)
Prog. no.
Level Standard value
Comfort setpoint
710
1010
1310
Eu
20.0 °C
Reduced temp setpoint
712
1012
1312
Eu
18 °C
Frost protection setpoint
714
1014
1314
Eu
10.0 °C
Heating curve slope
720
1020
1320
Eu
1,24
Heating curve displacement
721
1021
1321
E
0.0 °C
Heating curve adaption
Off | On
726
1026
1326
E
Off
Summer/winter heating limit
730
1030
1330
Eu
18°C
24-hour heating limit
732
1032
1332
E
0 °C
Flow temp setpoint min
740
1040
1340
E
8 °C
Flow temp setpoint max
741
1041
1341
E
80 °C
Flow temp setpoint room stat
742
1042
1342
E
- - - °C
Swi-on ratio room stat
744
1044
1344
E
- - -
Delay heat request
746
1046
1346
E
0 s
Room influence
750
1050
1350
C
- - - %
Room temp limitation
760
1060
1360
E
0.5 °C
Central heating boost
770
1070
1370
E
- - - °C
Quick setback
Off | Down to reduced setpoint | Down to frost prot
setpoint
780
1080
1380
E
Down to reduced
setpoint
Optimum start control max
790
1090
1390
E
0 min
Optimum stop control max
791
1091
1391
E
0 min
Reduced setp increase start
800
1100
1400
E
- - - °C
Reduced setp increase end
801
1101
1401
E
-15 °C
Continuous pump operation
No | Yes
809
1109
1409
E
No
Overtemp protect pump circ
Off | On
820
1120
1420
E
Off
Mixing valve boost
830
1130
1430
E
5 °C
Actuator running time
834
1134
1434
E
120 s
9 Settings
7636047 - 02 - 24082015
63
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...