ID-E342-001GB
57
The type and actuation variants are programmed only for a SAL element with a logical number
defined.
As far as the variants with zone dependence are concerned, the assigned zones may originate in their
own control panel (a standalone control panel) or in any control panels from the common detection
area (a control panel operating in a network).
The total number of zone assignments to all executive outputs and SAL type elements in the control
panel must not exceed 64,000.
Note:
-
The "Top" delay time is not applicable (equal to 0).
-
After completing the standard configuration and automatic declaration procedures, the SAL
type elements are assigned to a special logical number 0 and TYPE 0 is set, which makes them
inactive.
Detailed information regarding a SAL element itself is provided in the SAL-4001 Installation and
Maintenance Manual.
7.8 UCS 4000 UNIVERSAL CONTROLLING PANELS DECLARATION
The UCS 4000 (UCS in short) universal controlling panel is a standalone device enabling to control and
supervise fire protection devices, e.g. smoke exhaust dampers, doors, etc. (see the detailed description
provided in its Operation and Maintenance Manual). The UCS 4000 control panel may co-operate with
the POLON 4500 control panel through a detection line (connected to the circuit similarly to any other
line elements).
The POLON 4500 control panel may receive the following modes from the UCS 4000:
-
quiescent (also during operation of the air venting function in the UCS);
-
fire alarm (manual call point active - manual smoke extraction button connected to a dedicated
UCS input or alarm from a conventional detection line connected to UCS);
-
technical alarm (of the main relay [P1] and additional relays [P2, P3]) – acknowledgement of
output actuation in the UCS transformed into a fire alarm from the control panel;
-
non-maskable fault (from the monitored main relay [P1] and additional relays [P2, P3]) – lack of
actuation of an output in the UCS transformed into a fire alarm in the control panel;
-
testing – the UCS in a mode of testing elements and systems connected with a smoke exhaust
system;
-
UCS fault:
o
UCS power supply fault:
230 V power supply fault;
battery fault;
battery charging circuit fault;
voltage drop below 22 V;
earth fault;
o
UCS controller fault:
microprocessor or program memory fault;
EEPROM memory fault;
o
UCS main (P1) relay fault;
o
faults of UCS special dedicated inputs and outputs:
PA alarm relay fault (PSU-4000 module);
P2 or P3 individually programmed relays fault (PSD-4000 module);
conventional detection line fault (PSU-4000 module);
RPO (manual smoke exhaust button) line fault (PSU-4000 module);
fault of an output to alarm devices (PSU-4000 module);
power supply (fuse) of a rain/wind sensor fault (PSU-4000 module);
declared PSD-4000 module faulty or lack;
-
modes of an addressable module for communication with the POLON 4000 system:
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...