3.3 Ω ÷ 13 kΩ – quiescent mode (detection);
-
over 30 kΩ – fault mode (line break).
Lines are supplied with 18 V measuring voltage. An active mode of a monitoring line is triggered by
loading it with 1 kΩ characteristic resistance. In the quiescent mode, each monitoring line should be
loaded with a 10 kΩ end-of-line resistor connected to the end of this line.
Each of the 11 inputs may be programmed to perform the fK functions defined in Table 9.2.
Table 9.2 MSG-45 module monitoring lines functions
DETECTION
LINE fK
FUNCTION
NUMBER
DETECTION LINE FUNCTION
NAME
Indication by collective diodes in detecting unit
Line active mode effect
Line fault mode
0
INACTIVE LINE (SWITCHED OFF)
1
EXTINGUISHING START
2ND STAGE ALARM
FAULT
2
RELEASE START
2ND STAGE ALARM
(continuation)
FAULT
3
EXTINGUISHING STOP
BLOCKADE
FAULT
BLOCKADE
4
EXTINGUISHING BLOCKADE
BLOCKADE
FAULT
BLOCKADE
5
(ONLY) MANUAL CONTROL
MANUAL CONTROL
FAULT
6
E.A. RELEASE MONITORING
TECHNICAL ALARM
FAULT
7
PRESSURE/MASS MONITORING
TECHNICAL ALARM
FAULT
8
EXT. ALARM INPUT.
2ND STAGE ALARM
FAULT
9
NON-ELECTR. BLOCKADE
POSITION.
FAULT
10
E.A. DISCHARGE END
MONITORING
Permission for ACTUATION
MODE RESET
FAULT
11
UNIVERSAL MONITORING INPUT
TECHNICAL ALARM
FAULT
Other lines functionalities can be programmed in accordance with Table 9.3.
Table 9.3 MSG-45 module monitoring lines functions programming possibilities
Line
No.
Numbers and names of functions recommended
for monitoring lines assignation
Function choice range in
programming
Function
Default
No. *
1
1 - EXTINGUISHING START
0,
1
, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11
1
2
2 – RESERVE START
0, 1, 2, 3, 4, 5, 6 ÷ 11
0
3
3 - EXTINGUISHING STOP
0, 1, 2,
3
, 4, 5, 6 ÷ 11
3
4
4 - EXTINGUISHING BLOCKADE
0, 1, 2, 3, 4, 5, 6 ÷ 11
0
5
5 - (ONLY) MANUAL CONTROL
0, 1, 2, 3, 4,
5
, 6 ÷ 11
5
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...