ID-E342-001GB
129
APPENDIX A
POLON 4000 SYSTEM LINE ELEMENTY
Element description
Quiescent current
1)
DIO-4046 addressable ionisation smoke detector
150 µA
DOR-4046 addressable optical smoke detector
150 µA
DUR-4046 universal addressable optical smoke detector
150 µA
TUN-4046 addressable universal heat detector
120 µA
DOT-4046 addressable multi-sensor smoke and heat detector
150 µA
DPR-4046 addressable multi-sensor smoke detector
170 µA
DUT-6046 addressable multi-sensor smoke and heat detector
150 µA
DUR-4047 optical smoke radio detector
–
DOP-6001 optical line smoke detector
300 µA
ROP-4001, ROP-4001H manual fire call points
135 µA
ADC-4001 adapter (burdened with a side line):
- programmed in operation mode 1
- programmed in operation mode 2
- programmed in operation mode 3
- programmed in operation mode 4
- programmed in operation mode 5
- programmed in operation mode 6
6,8 mA
16,0 mA
2,5 mA
0,5 mA
2,2 mA
1,33 mA
ACR-4001 radio detectors adapter
6,0 mA
EKS-4001 monitoring and controlling element
145 µA
EWS-4001 multi-output controlling element
400 µA
EWK-4001 multi-input monitoring element
150 µA
SAL-4001 addressable acoustic signalling device:
- power supplied from battery or ext. source
- power supplied only from line
2)
150 µA
600 µA
UCS 4000 universal fire control panel
600 µA
UCS 6000 universal fire control panel
600 µA
1)
maximum current drawn by element from detection line/loop of POLON 4000 system control panel.
2)
signalling device without additional power supply must be provided with line/loop current for
alarming.
ID-E316-001GB/10.2011/02.2012
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...