9.4.2 Relay outputs functions general description
Most indicators may be programmed by assigning them different
fP
functions as necessary (see Table
9.4). The number of functions which may be assigned to some relays is limited (in order to eliminate
possible mistakes). See Table 9.5 for relay programming options.
See Table 9.6 for the criterion of relays actuation depending on the programmed function and time
parameters.
See Table 9.7 for the default settings for the MSG-45 module after the standard configuration procedure
is completed.
Table 9.4 MSG-45 module relays functions
fP Function
No.
Function Name
0
INACTIVE RELAY
1
ELECTROVALVE 1
2
ELECTROVALVE 2
3
ELECTROVALVE 3
4
ACTUATION SIGNALLING CONTROL
5
EVACUATION SIGNALLING CONTROL
6
WARNING SIGNALLING CONTROL
7
2ND STAGE ALARMU MODE SIGNALLING (EXTINGUISHING ZONE)
8
1ST STAGE ALARMU MODE SIGNALLING (EXTINGUISHING ZONE)
9
(ONLY) MANUAL CONTROL SIGNALLING
10
NON-ELECTRIC BLOCKADE SIGNALLING
11
EXTINGUISHING BLOCKADE SIGNALLING
12
EXTINGUISHING STOP MODE SIGNALLING
13
EXTINGUISHING START MODE SIGNALLING
14
DISCHARGE MODE SIGNALLING
15
SEALING
16
COMMON ELECTROVALVE