110
ID-E316-001GB
11.2 STANDARD CONFIGURATION/ACCESS CODES LOADING
A user may load the standard control panel settings. The standard configuration may be loaded only if it
is necessary to delete the previous configuration data (memory clearing) and create new configuration
from the very beginning.
To load the standard configuration
, restart the µPC microprocessor on the PSC-46 module with K1 key
of the SW1 switch actuated.
To load the factory access codes
, RESTART the µPC microprocessor with K3 key of the SW1 switch
actuated on the PSC-46 module.
Note:
The standard configuration loading process may take approx. 2 minutes. During this time, "NO
CONNECTION WITH µP1” message is displayed on the screen.
12 ACCESS CODES
The POLON 4500 control panel may be operated by four groups of people with different levels of
qualifications. The range of possible operations is divided into four levels – see Table 12.1.
Access to individual levels (apart from the 1
st
level) is authorised after entering an applicable access
code. An access code is a number containing from 4 to 8 digits.
The access codes at the 2
nd
and 3
rd
level may be changed (via software) after obtaining the 3
rd
level
access.
Table 12.1
Access level
Operator access
Allowable operations
1
st
*
no code necessary
alarm or fault ACKNOWLEDGEMENT, turning acoustic
signalling off, fire alarm readout, technical alarm readout,
fault readout, disablement readout and zone testing
readout
2
nd
**
2
nd
level access code
As per 1
st
level plus alarm RESET, PERSONNEL
PRESENT/PERSONNEL ABSENT switching over,
disablement, switching over to testing
3
rd
***
3
rd
level access
code
As per 2
nd
level plus control panel configuration except
modules and interface output declaration
4
th
****
4
th
level access
code
As per 3
rd
level plus hardware configuration change
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...