Activation mode time delay, max.
Output activation time delay, max.
Time programming ranges:
-
fire extinguishing signal delay
-
duration of impulses controlling electro valves (t1, t2, t3)
-
"sealing" delay
Types of push buttons installed in monitoring lines:
-
PU-61 - START EXTINGUISHING,
-
PW-61 - STOP EXTINGUISHING,
-
PB-61 - EXTINGUISHING BLOCKADE,
-
PD-61 - START RESERVE.
3 s
1 s
0 ÷ 60 s
0 ÷ 30 min.
0 ÷ 120 s
Fire extinguishing installation types:
-
high-pressure,
-
low-pressure,
-
neutral gases and extinguishing gas mixtures.
The MSG-45 modules additional functions (except for the functions required by the EN-12094-1
standard):
-
fire extinguishing signal delay,
-
receipt of the extinguishing agent flow signal,
-
subassembly status supervision,
-
receipt of signals emitted by emergency suspension devices,
-
separate supervision over the blocking device non-electric status,
-
discharge time control,
-
receipt of signals informing about operation modes changes - switching from the manual to
automatic/manual mode and vice versa,
-
transmission of actuating signals to the fire extinguishing installation devices,
-
actuation of an additional discharge,
-
signal transmission to devices outside the fire extinguishing installation,
-
receipt of signals emitted by emergency disconnecting devices,
-
extended outflow control,
-
actuation of alarm devices of different signals,
Control panel case ingress protection degree according to PN-EN 60259:2003
IP30
Operating temperature range
- 5 ºC ÷ + 40 ºC
Control panel mass
ca. 18 kg
Control panel dimensions
536x492x218 mm
PAR-4800 battery container dimensions
212x492x195 mm
Interoperation with devices:
-
computer keyboard,
-
computer,
-
the TELSAP 2100 digital monitoring system for,
-
the POLON 4000 (PMC-4000) digital monitoring system,
-
control panel co-operation with the TSR-4000 terminals – maximum
number of terminals connected to one control panel
16.
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...