80
ID-E316-001GB
Line
No.
Numbers and names of functions recommended
for monitoring lines assignation
Function choice range in
programming
Function
Default
No. *
6
6 – E.A. DISCHARGE MONITORING
0, 1, 2, 3, 4, 5, 6 ÷ 11
0
7
7 – PRESSURE/MASS MONITORING
0, 1, 2, 3, 4, 5, 6 ÷ 11
0
8
8 - EXTERNAL ALARM INPUT
0, 1, 2, 3, 4, 5, 6 ÷ 11
0
9
9 – NON-ELECTRICAL BLOCKADE POSITION
0, 1, 2, 3, 4, 5, 6 ÷ 11
0
10
10 – E.A. DISCHARGE END MONITORING
0, 1, 2, 3, 4, 5, 6 ÷ 11
0
11
11 - UNIVERSAL MONITORING INPUT
0, 1, 2, 3, 4, 5, 6 ÷ 11
0
* function default numbers are the functions numbers that have been assigned to monitoring lines after
factory programming or standard configuration loading
9.3.1 fK1 EXTINGUISHING START function
The EXTINGUISHING START function is performed in connection with the monitoring line no. 1 used to
supervise and transmit the signal for manual actuation of fire extinguishing from external
EXTINGUISHING START push buttons. One push button (or more push buttons in parallel) may be
connected to a monitoring line. See Fig. 9.2 for an example of a monitoring line circuit using a PU-61
push button. A LED indicates operation of the line and push button when it is pressed.
After the push button is pressed: