106
ID-E316-001GB
10.2 NETWORK PANEL FUNCTIONALITY
The console of a control panel operating in the network may work in three display and access modes:
-
local mode
– when a control panel with a local number is selected;
-
collective (group) mode
– when a control panel with number 0 is selected;
-
remote mode
– when a control panel with a different number is selected (it should exist in the
network).
Display and access modes may be changed at any moment by direct selection of a control panel number
and its confirmation with the Enter key or in the configuration menu.
The basic display mode for a control panel operating in the network is the collective mode.
10.2.1 Local mode
In the local mode (when the local control panel number is selected) the local control panel mode is
displayed. All readout and configuration functions relate to the control panel in which these actions are
taken. Signalling diodes and the acoustic signalling device indicate the internal mode of a local control
panel.
In order to select the local ("our") control panel, the access to its network number must be selected.
Then, the control panel shows (by means of its indicators) only the condition of this local control panel
(local detection area condition).
10.2.2 Collective mode
The collective mode is the basic mode for control panel operation in a network. In case the fire is
detected in the common detection area, the control panel automatically switches into the collective
operation mode.
In order to select the collective mode, the control panel No. 0 must be selected, which means that the
control panel indicators will display the condition of the common detection area for the control panel.
If no other control panels are assigned to the control panel (single control panel local detection area),
the indications for the local and common detection areas are identical.
Within the common detection area (when the control panel no. 0 [collective] is selected), the indicators
operate as follows:
-
FIRE indicator – global fire mode for the control panels of the common detection area;
-
ALARM indicator – global fire mode for the control panels of the common detection area; the
push button enables display of all alarming zones of the common detection area with control
panels numbers given;
-
FAULT indicator – global fault mode for the control panels of the common detection area; the
push button enables display of all control panel faults and general information regarding the
fault occurrence in co-operating control panels. Similarly to alarms, non-maskable faults can be
viewed in detail within the entire common detection area. In order to view the faults within the
remote control panel in detail, it is necessary to select the remote control panel and view its
faults.
-
DISABLEMENT indicator – global disablement mode for the control panels of the common
detection area; the push button enables display of all control panel disablements and general
information regarding the disablement occurrences in the control panels within the common
detection area. In order to view the disablements within the remote control panel in detail,
select the remote control panel and view its disablements.
-
TEST indicator – global testing mode for the control panels of the common detection area; the
push button enables display of all control panel tests and general information regarding the test
occurrences in the control panels within the common detection area. In order to view the fault
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...