10
ID-E316-001GB
Table 2.2
Item
Module name
Description
Quantity
1
2
3
4
5
6
MZ-48
MZ-48
MSL-1M
PPW-45
MSG-45
MIK-48
Melt fuse T 10L125 V
Melt fuse T3,15L250 V
Melt fuse F500L250 V
Melt fuse F1AL250 V
Melt fuse F1AL250 V
Melt fuse F500L250 V
1
1
1
1
1
1
Table 2.3
Item
Description
Drawing (catalogue) No.
1
2
3
4
5
6
7
MSG-45 extinguishing control module
MSI-48 mains module
PAR-4800 battery casing
Hanger
PAR-2000 battery casing
Bar code reader
Computer keyboard
B/E316-20.10.00
B/E270-70.00.00-1
A/E270-140.00.00-1
B/E297-04.00
3 TECHNICAL SPECIFICATIONS
Control panel supply voltage - mains 50 Hz
Maximum mains current consumption
Control panel internal operating voltage (DC)
Basic supply source:
-
AC power adaptor
Reserve supply source:
-
Pb ”24V” battery (airtight) cluster – capacity
Maximum internal resistance of the battery cluster plus supply cables resistance
Switching to reserve supply
Switching to battery charging
Maximum battery current consumption in the quiescent mode:
-
with 2 MSG-45 modules (without external devices current)
-
with 4 MSG-45 modules (without external devices current)
Maximum consumption of current supplied to external devices
from the power supply module terminals
Maximum total consumption of current supplied to external devices
in an alarm mode (including potential outputs)
Number of addressable detection lines
Maximum voltage in a detection line
Permissible quiescent current in a detection line (depending on configuration):
-
at maximum cabling resistance equal to 2 x 100 Ω
-
at maximum cabling resistance equal to 2 x 75 Ω
-
at maximum cabling resistance equal to 2 x 45 Ω
Maximum permissible resistance of detection line cabling
-
addressable line, depending on configuration
-
ADC-4001 side line
-
between two consecutive elements containing short circuit isolators
230 V +10 %-15 %
2.8 A
24 V + 25 %-15 %
30 V/10 A
38 ÷ 180 Ah
1 Ω
automatic
automatic
0.55 A
0.65 A
3 A
8 A
4
23.4 V ÷ 24.6 V
20 mA
22 mA
50 mA
2 x 100 Ω, 2 x 75
Ω
or 2 x 45 Ω
2 x 25 Ω
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...