ID-E342-001GB
53
5
0 ÷ 31
0 ÷ 1024
‘conjunction’ of 2
nd
stage alarms in assigned zones
6
0 ÷ 31
0 ÷ 1024
‘conjunction’ of 2
nd
stage alarms in assigned zones
7
b
b
reset output
Variant 0
Means lack of the EWS actuation criterion (permanently non-activated output).
Variant 1 – general 1
st
stage alarm
The output activation is performed in the case of a
1
st
stage alarm occurrence in the control panel or any
control panels of the common supervision area.
Variant 2 – ‘union’ of 1
st
stage alarms in assigned zones of the common supervision area control
panels
The output activation is performed in the case of a
1
st
stage alarm occurrence in at least one zone that is
assigned to this relay.
Variant 3 – ‘conjunction’ of 1
st
stage alarms in assigned zones of common supervision area control
panels
The output activation is performed in the case of a
1
st
stage alarm occurrence in at least two zones that are
assigned to this relay.
Variant 4 – general 2
nd
stage alarm
The output activation is performed in the case of a 2
nd
stage alarm occurrence in the control panel or any
control panels of the common supervision area.
Variant 5 – ‘union’ of 2
nd
stage alarms in assigned zones of the common supervision area control
panels
The output activation is performed in the case of a 2
nd
stage alarm occurrence in at least one zone that is
assigned to this relay.
Variant 6 – ‘conjunction’ of 2
nd
stage alarms in assigned zones of common supervision area control
panels
The output activation is performed in the case of a 2
nd
stage alarm occurrence in at least two zones that are
assigned to this relay
.
Variant 7 – reset output
The reset output is provided in order to generate a resetting impulse, lasting for ca. 1.5 s, after fire
alarm reset. This type can be utilized for instance for power supply and reset of detectors that require a
separate power supply, e.g. flame detectors manufactured by Det -Tronics.
Note:
Variant 7 is active only for the EWS element outputs 1 and 2.
Output relay actuation variants are programmed only for a EWS that possesses a logical number.
In the case of variant 2 and variant 5 application, at least one zone should be assigned to the EWS,
whereas in the case of variant 3 and variant 6 application, at least two zones should be assigned.
Variants 1 and 4 do not require any zone assignation.
In variants with zone dependence, the assigned zones can be allocated from own control panel (in the
case of independently operating control panel) or from any control panel of
the common supervision
area In the case of control panel network.
The total assignments of zones to all executive outputs and SAL type elements in the control panel
should not exceed 64,000.
Note:
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...