44
ID-E316-001GB
for the detection line cabling resistance at 2 x 75 Ω: . . . . . . . . . . . . . . . . . . . . . . 22 mA
for the detection line cabling resistance at 2 x 45 Ω: . . . . . . . . . . . . . . . . . . . . . . 50 mA
-
the detection line cabling capacity must not exceed 300 nF.
Fig. 6.1 POLON 4500 control panel addressable detection line examples
6.2 ADDRESSABLE ELEMENTS NUMBERING
In the POLON 4000 system, each addressable element has a unique 12-digit number (serial number) but
the control panel, during normal operation, refers to addressable elements via their element numbers
(short number - 1 ÷ 127 range). During the detection lines configuration, the serial numbers of
addressable elements are assigned to the consecutive element numbers.
There are three methods of addressable elements configuration in the POLON 4000 system:
-
automatic configuration
-
configuration with verification
-
manual numbering.