background image

Release Date: 05/01/2021 

Rev:01 

Warnings

 

General 

 

Read this manual carefully before operating the device and retain it for future reference 

 

Pay attention to all warnings and precautions described in the manual. 

 

Keep devices away from water and moisture utunuz. 

 
Service 

Do not attempt to repair the device by yourself, you may be exposed to electric shock if you open the device 

cover.  
In the event of any malfunction, contact your dealer or authorized service. Technical intervention to the device 

must be performed by qualified service personnel. 

 
 

 
 

 
Fault Conditions Requiring Service 

In the event of any malfunction or in the following cases, contact your authorized service or dealer. 

 

When the power cord or plug is damaged, 

 

When any liquid flows into the device or the object falls, 

 

When exposed to water and rain, 

 

If the device has been dropped or the housing has been damaged 

 

If the device has noticeable performance changes, 

 

If the device does not operate normally according to the operating instructions specified 

Call for service as incorrect operations can cause other malfunctions. 

 

Maintenance on your own  

Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any 
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have 

to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are allowed 
for cleaning. 

 

Transportation 

Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions 
that caused by improper transportation is not under warranty.  

 

Human and Environmental Health 

This device contains no chemical or biological elements that could harm human condition.  

Sub Models 
 

TFS-1183R 

Intelligent Addressable Flasher With Built-in Isolator, RED 

TFS-1183W 

Intelligent Addressable Flasher With Built-in Isolator, WHITE 

 

 

Technical Features

 

Power 

15VDC 

 32VDC (Nom.27VDC) 

Current Consumption 

~90 µA ( @27

VDC ) 

Alarm Consumption 

~Min.=4.31mA, Nom.=6.49 mA, Max.= 6.54mA. (27VDC ) 

Coverage 

W-2,4-4 

LEDs 

Wide Range 7 Bright LED RED 

Wide Range 7 Bright LED WHITE 

Heart Led 

White  20s period 

Red 20s period 

Protection Class 

IP21C 

Operating Temperature Range 

-10

C ~ 55

Flasher Mode 

3 (Slow, Normal, Fast) 

Humudity 

Between %0 - %95 at 

+40°C

 

Dimentions (mm) 

Ø:110mm, h:55mm (

Include Base Bracket) 

Body Material 

Red, UL94 Policarbonite 

White, UL94 Policarbonite 

Cable Selection 

0.8mm ² ~ 1.5mm ²

 

Weight (W 

 WO Base) 

207.7Gr. 

Usage 

Internal Usage / Siren Type : Type A 

 

Terminals

 

1 - 

Loop (-) IN 

2 - 

Loop (-) OUT 

3 - 

 

4 - 

Loop (+) IN, OUT 

 

EN 54-23 Visual Alarm Devices                

 

 

 

 
 

 

 

 
 
Mounting and Connection 

1.

 

Remove the head of the flasher from the base. 

2.

 

Mount the base part on the wall, using 2 of the 4 markings marked on the base.  

 

Attention: Do not attempt to remove the card from its plastic housing. Completely closed for 
your safety. Users must avoid Intervention

TFS-1183R / TFS-1183W 

Intelligent Addressable Flasher With Built-in 

Isolator 

Installation Manual 

Warning: The product only works with Teknim TFP-121x, Intelligent Addressable Fire 
Alarm panels