ID-E316-001GB
Fig. 4.3 Detection unit LED optical signalling devices
4 – FAULTY (ALARM TRANSMISSION DEVICES)
a) indicator - faults of outputs to alarm transmission devices:
- steady light - some or all outputs to alarm transmission devices are faulty.
5 – DISABLED (ALARM TRANSMISSION DEVICES)
a) indicator – disablements of outputs to alarm transmission devices:
- steady light - all outputs to alarm transmission devices are disabled;
- blinking light - some outputs to alarm transmission devices are disabled.
b) push button - turning on/off all outputs to alarm transmission devices (except for
permanently disabled outputs).
6 – ACTIVATED (ALARM DEVICES)
a) indicator - activation of at least one alarm output.
b) push button - turning on/off all outputs to alarm devices and the ones meeting the activation
criterion (except for permanently disabled outputs).
7 – FAULTY (ALARM DEVICES)
a) indicator - faults of some or all outputs to alarm devices.
8 – DISABLED (ALARM DEVICES)
a) indicator – disablements of outputs to alarm transmission devices:
- steady light - all outputs to alarm devices are disabled;
- blinking light - some outputs to alarm devices are disabled.
9 – ALARM
a) indicator - collective fire alarm indicator:
- steady light - fire alarm confirmed;
- blinking light - fire alarm unconfirmed.
b) push button - fast access to fire alarm messages.
10 – FAULT
a) indicator - collective fault indicator:
- steady light - fault confirmed;
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...