Tests may be carried out by operators at the 2
nd
or higher access level authorisation. The testing
procedures must be in accordance with the programming manual (PM).
8.3.1 TSO-4500 board signalling elements testing
During the test of signalling elements, all optical diodes and acoustic signals are actuated one after
another. When the test is finished, the control panel automatically returns to the standard operation
mode.
Testing is automatically stopped when the control panel receives a fire alarm signal. Moreover,
switching to the testing mode during fire alarm signalling is not possible.
The signalling elements test may always be stopped after pressing the ESC key.
8.3.2 Testing fire line elements in zone
The POLON 4500 control panel makes it possible to test line elements in an addressable line which
belong to any zone.
The procedure of switching into the testing mode of elements in a zone is carried out according to the
programming manual (PM). Switching a given zone into the test mode is signalled by steady light of the
yellow collective TESTING diode.
After an alarm signal is received from a line element, information regarding a test alarm is shown on the
LCD display and printed out (if a printer is connected).
The alarming element is cancelled in approx. 60 seconds.
The procedure of dis-actuating of the mode for testing elements (detectors) in a zone is carried out
according to the programming manual (PM). The collective TESTING diode is switched off (unless other
elements are tested).
A fire alarm from the zone which has not been switched into the testing mode results in automatic dis-
actuation of the testing mode and switching into fire alarm signalling in the control panel according to
the programmed variant.
Any number of line elements within the tested zone may be in the alarm mode at the same time,
however, for the inspection purposes, it is recommended to actuate line elements consecutively.
It is impossible to switch the system into the TEST mode within faulty or disabled zones or in case a fire
alarm is signalled.
The EKS-4001 monitoring and controlling elements tests consist in switching an element into the testing
mode, which should result in actuating an output relay. The element should indicate a correct relay
output condition.
8.3.3 EWS-4001 controlling elements testing
The EWS-4001 testing consists in switching individual relay outputs of an element into the testing mode,
which should result in activating the tested relay. The element should indicate a correct condition of the
relay output tested.
8.3.4 EWK-4001 monitoring elements testing
The EWK-4001 testing consists in forcing (by means of a characteristic resistor) a technical alarm mode
on individual inputs. The control panel should indicate a technical alarm mode for these inputs.
8.3.5 SAL-4001 acoustic signalling devices testing
The SAL-4001 testing consists in switching an element into a testing mode, which should result in
actuation of the required sound signals.
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...