an output type (TYPE-1 or TYPE-3);
-
variant (depending on the output type);
-
a set of assigned zones if it is required by a given variant (from the 1 ÷ 1024 range; from own
control panel or control panels of the common detection area).
Output types and variants
See Tables 7.3 and 7.4 for the programming possibilities of the SAL elements. The "control panel
number" parameter (only for control panels operating in a network) has the following meaning:
-
control panel number = 0 shows the dependence on an event in any control panel included in
the common detection area;
-
control panel number > 0 shows the dependence on an event from a given control panel
(provided it is included in the common detection area);
-
control panel number ”b” allows for making actuacon dependent only on local control panel
events.
For variants with additional zone dependencies: zone number = 0 shows the dependence on the total
number of events within all zones in a selected control panel included in the common detection area.
Type1
Table 7.3
Variant
Control
Panels
No.
Zones
Numbers
Time
Parameters
Actuation Criterion
1
0
b
T3
1
st
stage alarm in control panel (or control panel group
in case of network operation) or activation with
ACTIVATION push button in ALARM DEVICES area
2
0 ÷ 31
0 ÷ 1024
T3
1
st
stage alarm in assigned zones
Note:
The countdown of the delay time will be discontinued (T3 time will be reset during the countdown time)
and the outputs to alarm devices will be activated immediately after the control panel enters the 2
nd
stage alarm mode. After setting the T3 parameter to maximum time (10 minutes), the actuation
criterion may be dependent on "the 2
nd
stage alarm only".
Type 3
Table 7.4
Variant
Control
Panels
No.
Zones
Numbers
Time
Parameters
Actuation Criterion
1
0
b
T
op
1
st
stage alarm in control panel
2
0
b
T
op
1
st
stage alarm in control panel until acknowledgement
3
0
b
T
op
2
nd
stage alarm in control panel
4
0
b
T
op
2
nd
stage alarm in control panel until acknowledgement
5
0 ÷ 31
0 ÷ 1024
T
op
1
st
stage alarm in assigned zones
6
0 ÷ 31
0 ÷ 1024
T
op
1
st
stage alarm in assigned zones until acknowledgement
7
0 ÷ 31
0 ÷ 1024
T
op
2
nd
stage alarm in assigned zones
8
0 ÷ 31
0 ÷ 1024
T
op
2
nd
stage alarm in assigned zones until acknowledgement
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...