62
ID-E316-001GB
The output activation is performed in the case of a 2
nd
stage alarm occurrence in at least two zones that are
assigned to this relay
.
In the case of variant 2 and variant 5 application, at least one zone should be assigned to an UCS,
whereas in the case of variant 3 and variant 6 application, at least two zones should be assigned.
Variants 1 and 4 do not require any zone assignation.
In the case of variants with zone dependence, the assigned zones are allocated to own control panel (an
alone panel) or to control panels
of the common supervision area (panels operating in a network).
The total number of zones assignments to all executive outputs and SAL type elements in the control
panel should not exceed 64,000.
Note:
A non-maskable fault is also not signalled if the output is settled at variant 0.
After the standard configuration loading and automatic configuration performance, UCS elements are
assigned to a special logical number 0, which causes that such an element is inactive.
7.10 TSR-4000 TERMINALS DECLARATION
A TSR-4000 terminal is a remote device to signal the POLON 4000 system control panel modes. Up to 16
terminals may be connected to one control panel and an RS-485 serial interface is responsible for
transmission.
The declaration of terminals consists in selecting the SYSTEM CONFIGURATION -> HARDWARE
DECLARATION -> TSR-4000 TERMINAL DECLARATION option for the declared terminal numbers of one of
the two following options: WITH ACCESS and WITHOUT ACCESS. WITH ACCESS shows the permission for
remote operation of the control panel and the fact that a terminal may remotely acknowledge an alarm
or fault and remotely reset the control panel alarm.
8 FUNCTIONALITY DESCRIPTION
8.1 ALARMING
8.1.1 Alarm types
After a line element in an addressable detection line is actuated, the POLON 4500 control panel, on the
basis of the decision algorithms, generates the PRELIMINARY ALARM, 1
st
stage alarm or 2
nd
stage alarm
depending on the alarming variants programmed for given zones (rooms).
A preliminary alarm is signalled by means of the internal acoustic signalling system and a red diode in
the ALARM field.
The LCD display shows a window marked as !!! PRELIMINARY ALARM !!! and the information regarding
the number of alarming zones and the number of zones not shown on the display (due to limited space)
is displayed in a separated field below. The main alarm window displays messages assigned to the
alarming zones. If the number of alarming zones is too big to display them simultaneously, i.e. more
than 8 zones, the alarms which are not displayed may be viewed by means of the ALARM push button.
A preliminary alarm is an internal alarm and may be acknowledged with the ACKNOWLEDGEMENT push
button and reset with the RESET push button.
Note:
A preliminary alarm may be transformed into a fire alarm or automatically cleared by the control panel
according to the applicable algorithms resulting from alarming variants for zones.
1
st
stage alarm
is signalled by fast flashing of a big red FIRE indicator and an additional diode in the
ALARM field.
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...