ID-E342-001GB
111
*
for the control panel direct servicing personnel
**
for the direct servicing personnel or the maintenance technician
***
for a person being authorised for program configuration change
**** for the manufacturer and authorised servicing company for hardware configuration change.
Note:
Using the EXTINGUISHING START, EXTINGUISHING STOP, RESERVE START and EXTINGUISHING
DISABLEMENT push buttons in the fire extinguishing zones is possible only in conjunction with the
PERMISSION push button protected with a sealed casing against unauthorised use.
The above mentioned push buttons may be used without any access code. They execute functions
(apart from the PERMISSION push button) identical to their corresponding external push buttons in the
fire extinguishing zones.
13 INSTALLATION
13.1 CONTROL PANELS INSTALLATION LOCATION
The POLON 4500 control panels should usually be installed in rooms included in 24-h duty. In case the
control panel installation location is not included in 24-h duty, signals from the unit must be transmitted
to the locations where the personnel is on constant duty by means of the monitoring system or contacts
of the relays for additional signalling.
A control panel must be installed in a visible, easily accessible location, protected against direct sunlight
and heat sources.
The ambient temperature must not be lower than 0
o
C and higher than +40
o
C. In rooms with high noise
emission, use external acoustic signalling devices controlled with signal lines of relay contacts located on
the PPW-45 module.
Control panels are mounted on walls by means of the special supporting frame delivered with the
device.
A manual call point should be installed in the vicinity of a control panel (in sight distance).
13.2 POWER SUPPLY CONNECTION
In order to connect the mains power supply cabling to the control panel, use the three terminals located
on the mains connection board on the back wall between the AC power adaptor and the PZ-48 power
supply module. The power supply cable may be routed to the control panel through a round seal located
over the mains connection board. The method of connecting the mains power supply is presented in Fig.
The mains terminals are covered with the insulating cover marked as ~230 V/50 Hz. Wire indications are
provided next to applicable terminals. Wires must be connected to proper terminals, according to their
purpose. The PE protection wire must be connected directly to the collective grounding terminal above
the PZ-48 module on the control panel housing and to the PE terminal of the mains connecting terminal
line.
The emergency power supply (batteries) must be connected after the mains power supply is connected.
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...