ID-E342-001GB
107
tests within the remote control panel in detail, select the remote control panel and view its
tests.
-
TECHNICAL ALARM indicator – global technical alarm mode for the control panels of the
common detection area; the push button enables display of all control panel technical alarms
and general information regarding the technical alarm occurrences in the control panels within
the common detection area. In order to view the technical alarms within the remote control
panel in detail, select the remote control panel and view its technical alarms.
-
ACKNOWLEDGEMENT indicator – global mode of the indicator for the control panels of the
common detection area; the push button enables acknowledgement of all events in the control
panels within the common detection area.
-
RESET indicator – shows the possibility of cancelling a local control panel alarm or locally
received alarm from the control panels of the detection area; the push button resets an alarm in
the control panels within the common detection area.
-
Other indicators, i.e. PERSONNEL ABSENT, DELAYS OFF, POWER SUPPLY, ALARM DEVICES and
ALARM TRANSMISSION DEVICES, show the local control panel mode.
In order to view the events in a remote control panel, select this panel and proceed similarly to viewing
the events in a local control panel.
In the collective mode, if a remote control panel is declared for co-operation as one of the control
panels within the common detection area, even after disabling the remote operation in this control
panel, it is still possible to remotely operate the ACKNOWLEDGEMENT and RESET push buttons.
In the collective mode, all programming, disablement, testing and programming review functions relate
to the control panel with the local number.
10.2.3 Remote mode
In the remote mode, it is possible to select access to any "remote" control panel (also outside the
common detection area) and view its software resources and condition (i.e. faults, disablements, event
memory, etc.).
In the remote mode, when the number of a different control panel is selected, the remote control panel
mode is displayed on the operator's panel. All readout and configuration functions relate to the remote
control panel. In this mode, the real condition of the remote control panel is displayed without
displaying the common (collective) condition of a distant control panel. For example, if an alarm from a
different control panel within the common detection area is generated in the remote control panel,
detection is remotely visible in this control panel since no zones belonging to this control panel is in the
alarm mode.
The possibility of changing the condition and modifying the configuration resources in the remote
control panel depends on the remote operation option programmed in this panel.
Three levels of remote access to a remote control panel may be programmed in this panel. They
correspond to the access levels in a local control panel. The 4
th
level is remotely forbidden (disabled).
The remote access may be disabled (recommended) but it does not mean that the access is fully denied
to this control panel as its condition and software resources may still be reviewed.
After selecting a "remote" control panel, the indicators of "our" local control panel show the mode of
the indicators installed in the former. The possibility of using the operating push buttons (in order to
change its mode) depends on the provided level of "remote operation" in the remote control panel.
Note:
Common detection areas should be created as follows:
-
Hierarchical group: among n allocated control panels only one k control panel (collective control
panel) has the remaining n-1 control panels declared to the common detection area.
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...