ID-E342-001GB
17
- blinking light - fault unconfirmed.
b) push button - fast access to fault messages.
11 – DISABLEMENT
a) indicator - collective disablement indicator:
- steady light - disablement turned on.
b) push button - fast access to disablement messages.
12 – TESTING
a) indicator - collective testing indicator:
- steady light - testing activated.
b) push button - fast access to testing messages.
13 – TECHNICAL ALARM
a) indicator - collective technical alarm indicator:
- steady light - technical alarm confirmed;
- blinking light - technical alarm unconfirmed.
b) push button - fast access to technical alarm messages.
14 – PERSONNEL ABSENT
a) indicator - Personnel Absent mode.
b) push button - turning on/off the Personnel Absent mode.
15 – DELAYS OFF
a) indicator - delays turned off.
b) push button - turning on/off all delay times (T1, T2, T3, Top).
16 – SYSTEM FAULT
a) indicator - system (processor circuits) fault.
17 – POWER
a) indicator - control panel power supply:
- steady light - control panel supplied from the mains; no faults;
- blinking light - any power supply fault.
4.3.3 Extinguishing unit LED optical signalling devices
1 - MANUAL CONTROL
a) indicator:
- ON - only manual control;
- OFF - automatic and manual control.
b) push button - turning on/off manual control.
2 - FAULT
a) indicator - collective fault indicator:
- steady light - fault in a fire extinguishing zone.
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...