30
ID-E316-001GB
At any given time, the outputs to fire alarm transmission devices may be disabled and re-enabled
(excluding outputs permanently disabled within the program) at a given access level by using the push
button on the control panel front panel marked: ALARM TRANSMISSION DEVICES – DISABLED.
The output actuation is signalled by the red LED in the following field:
ALARM TRANSMISSION DEVICES – ACTIVATED.
The output disablement is signalled by the yellow LED in the following field:
ALARM TRANSMISSION DEVICES – DISABLED - flashing - some outputs disabled; steady - all outputs
disabled.
The output fault is signalled by the yellow LED in the following field:
ALARM TRANSMISSION DEVICES – FAULTY.
5.5.5 Protecting devices output (TYPE 3)
Outputs to protecting devices may be programmed in the following variants:
Table 5.6
Variant
Control
Panel
Nos
Zone
Nos
Time
Parameters
Activation Criterion
1
0
b
T
op
1
st
stage alarm in control panel
2
0
b
T
op
1
st
stage alarm in control panel until acknowledgement
3
0
b
T
op
2
nd
stage fire alarm in control panel
4
0
b
T
op
2
nd
stage alarm in control panel until acknowledgement
5
0 ÷ 31
0 ÷
1024
T
op
1
st
stage alarm in assigned zones
6
0 ÷ 31
0 ÷
1024
T
op
1
st
stage alarm in assigned zones until
acknowledgement
7
0 ÷ 31
0 ÷
1024
T
op
2
nd
stage alarm in in assigned zones
8
0 ÷ 31
0 ÷
1024
T
op
2
nd
stage alarm in assigned zones until
acknowledgement
5.5.6 Fault/technical alarm signalling output (TYPE 4)
The output of the fault signalling system may be programmed in the following variants:
Table 5.7
Variant
Control
Panel
No.
Zones/EKS/EWK
Numbers
Time
Parameters
Activation Criterion
1
0 ÷ 31
b
T
op
General fault in control panel
2
0 ÷ 31
b
T
op
General non-maskable fault in control panel
3
0 ÷ 31
b
T
op
General technical alarm in control panel
4
0 ÷ 31
b
T
op
General fault in control panel until
acknowledgement
5
0 ÷ 31
b
T
op
General non-maskable fault in control panel until
Summary of Contents for 4000
Page 25: ...ID E342 001GB 25 Fig 5 3 MSL 1M line module overview ...
Page 96: ...96 ID E316 001GB Fig 9 16 Non potential output exemplary connection ...
Page 101: ...ID E342 001GB 101 Fig 10 2 MSI 48 and MSI 48 Ed 3 network modules ...
Page 103: ...ID E342 001GB 103 Fig 10 3 Four control panels network connection with two pairs of cables ...