100
ID-E316-001GB
The control panel number may be expressed by means of the following formula:
CONTROL PANEL NO. = W1*1 + W2*2 + W3*4 + W4*8 + W5*16
where:
Wn=0, if Kn key is in OFF position
Wn=1, if Kn key is in ON position
E.g. control panel numbered as 9 has the following keys settings:
K1 - ON
K2 - OFF
K3 - OFF
K4 - ON
K5 – OFF
CONTROL PANEL NO. = 1*1 + 0*2 + 0*4 + 1*8 + 0*16 = 9
Keys K6, K7, K8 currently are not used.
The MSI-48 module is equipped with ZW1 ÷ ZW4 or ZW1 ÷ ZW6 (Ed.3) programming jumpers which
should be set in the position shown in Fig. 10.2.
Additionally, the module is equipped with 8 service diodes (D1 ÷ D8) which may be tuned off by setting
the ZW5 or ZW8 (Ed.3) in position 2-3, which results in decreasing the total current consumption of the
module.