background image

TFB-1166 v2 

INTELLIGENT ADDRESSABLE MANUAL CALL POINT WITH BUILT-IN ISOLATOR, RESETTABLE 

Installation and User Manual 

Release Date: 04/01/2021 Rev:03 

IMPORTANT WARNINGS 

  GENERAL 

 Read this manual carefully before operating the equipment and save 

it for future reference. 

 Observe  all  warnings  and  precautions  specified  in  the  operating 

instructions. Follow all operating and usage instructions. 

 Keep devices away from water and moisture. 

  ENVIRONMENTAL CONDITIONS 

Do  not  operate  the  device  in  extremely  hot  or  cold  environments 
except under the following conditions. 

 

Temperature: 

Between -10

C ~ +70

 

Humidity: 

93% at 

+40°C   

   SERVICE 

Do not attempt to repair the appliance yourself, you may be exposed 
to electric shock if you open the appliance cover. 

In  the  event  of  any  malfunction,  contact  your  dealer  or  authorized 
service.  Technical  intervention  to  the  device  must  be  performed  by 
qualified service personnel. 

FAULT CONDITIONS REQUIRING SERVICE 

In  the  event  of  any  malfunction  or  in  the  following  cases,  contact 
your authorized service or dealer.

 

 

  When the power cord is damaged, 

  When any liquid flows into the device or any object falls, 

  When exposed to water or rain, 

  If  the  device  has  been  dropped  or  the  housing  has  been 

damaged 

  If the device has noticeable performance changes, 

  If  the  device  does  not  operate  normally  according  to  the 

operating instructions specified in the installation manual  

WHAT YOU CAN DO ON YOURSELF   

Do  not  attempt  to  repair  the  appliance  yourself,  as  you  may  be 
exposed to  electric  shock  if you  open  the  case. In the  event  of  any 
malfunction,  contact  your  dealer  or  authorized  service.  Technical 
intervention  to  the  device  must  be  carried  out  by  qualified  service 
personnel. The appliance should be cleaned with a dry cloth. Do not 
use any chemicals.  

SHIPMENT AND TRANSPORTATION 

The device must be handled carefully so that it is not exposed to any 
external impact and does not allow any liquid to enter. Malfunctions 
during improper handling are not covered by the warranty.

 

 

 HUMAN AND ENVIRONMENTAL HEALTH 

 

This device does not contain any chemical or biological substances that may 

harm human health.

 

 

 

 

 

 

 

 

 

 

  

CE 

 

1922 

Bilgi Elektronik San. ve Tic. A.Ş. 

Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi 

No:1 Kat:2 No:32 Ümraniye / İstanbul 

17 

1922-CPR-0898 

EN 54-11:2001, EN 54-11:2001/A1:2005 
Manual Alarm Devices 

TFB-1166 

Technical Data: 

See BİLGİ-TEC-170907-2 maintained at the 

manufacturer 

INSTALLATION AND CONNECTION 

1.  Mount the button on the wall so that the fire cable passes 

through the base of the clip. Do not over-tighten the wall-
mounting screws. 

 

 

2.  On  the  board  there  are  LIN+,  LIN-,  EARTH,  LOUT-  and 

LOUT+  connectors.  For  the  perfect  operation  please 
c from control panel loop exit toLIN+ and 

– from 

control  panel  loop  exit to  LIN-.  And  move  to next  device 
from LOUT- and LOUT+  

 

 

 
3.  EARTH  connection  must  be  connected  both  on  control 

panel and inside of manual call point to ensure integrity 
 

4.  After  the  TFB-1166  is  connected  to  the  panel  and  give 

address,  the  LED on  it  starts to  blink  with  a  blue  light at 
intervals  of  20  seconds.  LED  lights  steady  RED  in  case 
of  alarm.  If  a  short  circuit  occurs  on  the  loop  line,  the 
YELLOW  LED  on  the  call  point  lights  up  continuously 
and  the  short  circuit  point  is  opened  by  two  isolators  to 
protect the loop line. 

 
 
 
 

Warning: TFM-128x Sub-base isolator modules must be 
operated together with v2 version Addressable Panel, 
TFC-1201 Loop Board, TFM-128X Sub-Base Modules and 
TFM-1990 Isolator Module. Short circuit protection 
function does not work if used with previous versions

!  

Make sure that the following label is on the products that will 
work with short circuit protection function. 

 

 

 

 

 

Reviews: