Table 67 Rack specifications for a Pillar Axiom 600 system (continued)
Criteria
Pillar rack
Non-Pillar rack (minimum
requirements)
Depth (outside)
39.5 inches (100.3 centimeters)
43 inches (109.2 centimeters)
maximum
Front door
● Vented
● Light-tint Plexiglas
● 1.5 inches (3.81 centimeters)
deep
● Lockable
● Open left/right
● 1 inches (2.54 centimeters)
clearance between front vertical
channel and inside of frame
● Vented
● 1 inches (2.54 centimeters)
deep minimum
● 1 inches (2.54 centimeters)
clearance between front
vertical channel and inside
of frame
Rear door
● Vented
● Lockable
● Open left/right
Vented
Sides
● Solid
● Removable
● Lockable
● 1 inches (2.54 centimeters)
between side and frame
N/A
Vertical
channels
● Square hole, unthreaded
● 26 inches (66 centimeters) apart
● EIA spacing
● Front-to-rear mounting
● Cage nuts
● Square EIA-standard
mounting holes required
We recommend that Pillar racks
be used to install Pillar Axiom 600
hardware components.
Vents
● Front and back doors
● Top
● Front and back doors
● Top
PDU
● 4 PDUs
● 90–240VAC, 50-60Hz
● 20-30A
● Redundant power
● 90–240VAC, 50–60Hz
● Wattage: 8350W
Appendix C Pillar Axiom Hardware Specifications
Pillar Rack Hardware Specification
202