Pillar Axiom 600 PDU Hardware Specification
If you install non-Pillar PDUs, they must meet the Pillar Axiom 600 PDU
specification, as outlined below.
When you intend to use non-Pillar PDUs, check first with your Pillar Account
Representative to ensure you do not jeopardize your system warranty by
installing the non-Pillar PDUs.
Table 66 PDU specifications
Criteria
20A single-phase
30A single-phase
3-phase
Form factor
EIA Rack
Mountable
Height: 1U, or
1.75 inches
(4.45 centimeters)
Depth: < 8 inches
(20.3 centimeters)
EIA Rack
Mountable
Height: 1U, or
1.75 inches
(4.45 centimeters)
Depth: < 8 inches
(20.3 centimeters)
EIA Rack
Mountable
Height: 2U, or
3.5 inches
(8.9 centimeters)
Depth: 9.5 inches
(24.13 centimeters)
Receptacles
IEC 60320
C13, 12
receptacles
minimum.
Mounted on rear
of chassis
(opposite circuit
breakers).
C13, 12
receptacles
minimum. Mounted
on rear of chassis
(opposite circuit
breakers).
C13, 24
receptacles (8 per
phase) minimum.
Mounted on back
of chassis
(opposite circuit
breakers).
Inlet cable
15 feet
(4.572 meters)
minimum
Plug options:
L6-20P, L5-20P
IEC 2P+E 16A
15 feet
(4.572 meters)
minimum
Plug options:
L6-30P, L5-30P
IEC 2P+E 32A
15 feet
(4.572 meters)
minimum
NEMA L21-30P
IEC 3P+N+E 16A
6H
Voltage input
100–240VAC
100–240VAC
120/208VAC,
230/400VAC, both
Wye Configuration
Voltage
output
100–240VAC
100–240VAC
120V 1-phase,
230V 1-phase
Appendix C Pillar Axiom Hardware Specifications
Pillar Axiom 600 PDU Hardware Specification
199