Table 66 PDU specifications (continued)
Criteria
20A single-phase
30A single-phase
3-phase
Circuit
breakers
(CB)
Two, 10A each.
Each circuit
breaker controls
half of the outlet
receptacles.
Two, 15A each.
Each circuit
breaker controls
half of the outlet
receptacles.
One main, 30A
Three secondary,
20A each
Receptacle
retention
device
All receptacles
have a plug
retention device.
All receptacles
have a plug
retention device.
All receptacles
have a plug
retention device.
Inlet cable
retention
device
If a detachable
inlet cable is
provided, a cable
retention device is
included.
N/A
N/A
EMI (RFI)
filter
Common mode
insertion loss:
10 db @ 1MHz,
Differential mode:
30 db @ 1MHz.
MHz/db: .15/6, .50
Common mode
insertion loss:
10 db @ 1MHz,
Differential mode:
30 db @ 1MHz.
MHz/db: .15/6, .50
Common mode
insertion loss:
25 db @ 1MHz.
Differential mode:
22 db @ 1MHz.
MHz/db: .15/6, .50
Surge
suppression
270VAC
320VAC
275VAC
Appendix C Pillar Axiom Hardware Specifications
Pillar Axiom 600 PDU Hardware Specification
200