50
Control interfaces
(1) Menupossible only with pump stopped.
(2) Menu accessible only if [ROOTS 2 OPTION] is [ENABLED].
(3) Menu accessible only if [DELAY STOP ALARM] is [ENABLED].
(4) Menu available if [INLET VALVE][AUTO SOFT PUMPING] or [MANU SOFT PUMPING] is activated.
(5) Menu available if at least one of the [HEATER 1T°],[HEATER 2T°] or [HEATER 3T°] is set on CON-
TROL.
TEMPERATURE
HEATER ALARMS
(5)
DEFAULTS
PRE-ALARM DESABLED
ENABLED
Delay
0-600 s
WARNING
DESABLED
ENABLED
Delay
0 s
EXH PRESSURE
HIGH DEFAULTS
WARNING
Threshold
500-1990 mbar
Delay
0-600 s
PRE-WARNING
DISABLED
ENABLED
Threshold
500-1650 mbar
Delay
0-600 s
ALARM
Threshold
1990 mbar
Delay
0-5 s
(3)
PRE-ALARM
DISABLED
ENABLED
Threshold
1650-1990 mbar
Delay
0-600 s
LOW DEFAULTS
WARNING
Threshold
550 mbar
Delay
10 s
U LINE
HIGH DEFAULTS
WARNING
DISABLED
ENABLED
Threshold
185-550 V
Delay
0-600 s
LOW DEFAULTS
WARNING
DISABLED
ENABLED
Threshold
160-265 V
Delay
0-600 s
SOFT PUMPING VALVE
(4)
Delay
0-600 s
LOGIC INPUT
LOG1
DISABLED
ENABLED
Sensor type
NO/NC
DEFAULTS
ALARM
DISABLED
ENABLED
Delay
0-600 s
WARNING
DISABLED
ENABLED
Delay
0-600 s
LOGIC INPUT
LOG2
DISABLED
ENABLED
Sensor type
N0/NC
DEFAULTS
ALARM
DISABLED
ENABLED
Delay
0-600 s
WARNING
DISABLED
ENABLED
Delay
0-600 s
LOGIC INPUT
LOG3
DISABLED
ENABLED
Sensor type
NO/NC
DEFAULTS
ALARM
DISABLED
ENABLED
Delay
0-600 s
WARNING
DISABLED
ENABLED
Delay
0-600 s
ANALOGIC INPUT ANA 1
DISABLED
MEASUREMENT HIGH DE-
FAULTS
ALARM
DISABLED
ENABLED
Threshold
0-10000 mV
Delay
0-600 s
WARNING
DISABLED
ENABLED
Threshold
0-10000 mV
Delay
0-600 s
USER ANA
DISABLED
MEASUREMENT HIGH DE-
FAULTS
ALARM
DISABLED
ENABLED
Threshold
0-10000 mV
Delay
0-600 s
WARNING
DISABLED
ENABLED
Threshold
0-10000 mV
Delay
0-600 s
SERIAL LINK
SERIAL J2
(see
Serial link
Operating instructions)
SERIAL J6
(see
Serial link
Operating instructions)
SERIAL J7
(see
Serial link
Operating instructions)
DATE AND TIME
DAY
0-31
MONTH
1-12
YEAR
0-99
HOUR
0-23
MINUTE
0-59
SETTING
(1)
Selection
Setting range
Summary of Contents for A 1204H
Page 88: ...ETL Mark...
Page 89: ...Certificate of conformance to SEMI...