Installer manual Fleck 3150 NXT/NXT2 - Programming
Ref. MKT-IM-010 / C - 18.10.2019
93 / 182
Parameter
Options
Definition
Note
AUXILIARY 1
STANDBY
Activates relay from beginning of
regeneration and during standby
phase.
OFF
(default)
ALARM
BASED
-
Any alarm or error detected by
the controller will start signal
output from Auxiliary relay#1.
CYCLE
BASED
-
TIME
BASED
-
VOLUME
BASED
-
This choice will only available
when metered regeneration
type.
AUX. 1: CYCLE
BASED
SP
Service position
Only displayed if “Cycle based”
is chosen for auxiliary 1;
Activate or de-activate for each
position (
= deactivated;
= activated).
BW
Backwash position
BD
Draw and slow rinse
position
RR
Rapid rinse position
RF
Refill position
SB
Pause position
AUX. 1: TIME
BASED - START
TIME #1
0 to total
regeneratio
n time
minus
1 minute
Minute
Only displayed if “Time based” is
chosen for auxiliary 1.
AUX. 1: TIME
BASED - END
TIME #1
from start
time#1 plus
1 minute
until total
regeneratio
n duration
Minute
AUX. 1: TIME
BASED - START
TIME #2
OFF
End time #1
to total
regeneratio
n duration
minus
1 minute
Minute
Only displayed if “Time based” is
chosen for auxiliary 1 and END
TIME #1< total regeneration
duration minus 1 minute;
Range depend on Start and end
time #1 values.
Summary of Contents for FLECK 3150 NXT
Page 1: ...FLECK 3150 NXT NXT2 INSTALLER MANUAL WATER PURIFICATION ...
Page 139: ...Installer manual Fleck 3150 NXT NXT2 Maintenance Ref MKT IM 010 C 18 10 2019 139 182 DC motor ...
Page 144: ...Installer manual Fleck 3150 NXT NXT2 Maintenance 144 182 Ref MKT IM 010 C 18 10 2019 ...
Page 148: ...Installer manual Fleck 3150 NXT NXT2 Maintenance 148 182 Ref MKT IM 010 C 18 10 2019 ...
Page 182: ...www pentairaquaeurope com ...