Installer manual Fleck 3150 NXT/NXT2 - Programming
Ref. MKT-IM-010 / C - 18.10.2019
113 / 182
a) Set the relay Start time #2 with
and
;
b) Can be adjusted from: end time #1 +1 to the total
regeneration duration minus 1 minute;
c) Press to validate the selection and advance to the
next parameter;
d) Set the relay End time #2 with
and
;
e) Can be adjusted from: start time #2 + 1 to the total
regeneration duration;
f) Press to validate the selection and advance to the
next parameter.
Activated 12 minutes
after the regeneration
started.
TIME BASED - START
TIME #2.
Deactivated 150 minutes
after the regeneration
started.
TIME BASED - END
TIME #2.
Volume based (Chemical pump)
Activate the relay output during the service for a preset duration based upon the
volume of treated water.
Info
Only visible if "volume based" was selected as auxiliary in the previous step.
Info
Only visible in metered systems.
Info
This parameter has two steps. The first one determines the volume which activates the
relay. The second one determines how long the relay has to be activated once the
volume has passed.
a) Set the relay activation volume with
and
;
b) Can be adjusted from: 1L to the total capacity of a
service cycle excluding the reserve capacity.;
c) Press to validate the selection and advance to the
next parameter;
d) Set the relay activation duration with
and
;
e) Can be adjusted from: 1 to 7200 seconds;
f) Press to validate the selection and advance to the
next parameter.
Activates upon 1 L.
VOLUMEBASED-
VOLUME-L.
Deactivates upon
10 minute.
VOLUMEBASED-
DURATION-S.
Summary of Contents for FLECK 3150 NXT
Page 1: ...FLECK 3150 NXT NXT2 INSTALLER MANUAL WATER PURIFICATION ...
Page 139: ...Installer manual Fleck 3150 NXT NXT2 Maintenance Ref MKT IM 010 C 18 10 2019 139 182 DC motor ...
Page 144: ...Installer manual Fleck 3150 NXT NXT2 Maintenance 144 182 Ref MKT IM 010 C 18 10 2019 ...
Page 148: ...Installer manual Fleck 3150 NXT NXT2 Maintenance 148 182 Ref MKT IM 010 C 18 10 2019 ...
Page 182: ...www pentairaquaeurope com ...