Remove a Power Supply
96
Oracle Server X5-2L Service Manual • May 2015
3.
Gain access to the rear of the server where the faulty power supply is located.
4.
If the cable management arm (CMA) is installed, disconnect both CMA left-side
connectors and move the CMA out of the way.
For instructions for disconnecting the CMA left-side connectors, refer to
“Remove the Cable
Management Arm” in “Oracle Server X5-2L Installation Guide ”
.
Caution -
When disconnecting the CMA left-side connectors, be sure to use your arm to
support the CMA so that it does not hang down under its own weight and stress the right-side
connectors; otherwise, the CMA might be damaged. You must continue to support the CMA
until you have reconnected both of the left-side connectors.
5.
Disconnect the power cord from the faulty power supply.
6.
Grasp the power supply handle and push the power supply latch to the left [1].
FIGURE 24
Removing a Power Supply
7.
Pull the power supply out of the chassis [2].
Caution -
Whenever you remove a power supply, you should replace it with another power
supply; otherwise, the server might overheat due to improper airflow.
8.
Continue to
“Install a Power Supply” on page 97
.
Summary of Contents for X5-2L
Page 1: ...Part No E48333 04 May 2015 Oracle Server X5 2L Service Manual ...
Page 2: ......
Page 12: ...12 Oracle Server X5 2L Service Manual May 2015 ...
Page 24: ...24 Oracle Server X5 2L Service Manual May 2015 ...
Page 50: ...50 Oracle Server X5 2L Service Manual May 2015 ...
Page 70: ...70 Oracle Server X5 2L Service Manual May 2015 ...
Page 100: ...100 Oracle Server X5 2L Service Manual May 2015 ...
Page 268: ...268 Oracle Server X5 2L Service Manual May 2015 ...
Page 292: ...292 Oracle Server X5 2L Service Manual May 2015 ...