Remove the Storage Drive Backplane for Twenty-Four Drive Systems
158
Oracle Server X5-2L Service Manual • May 2015
Related Information
■
“Remove the Storage Drive Backplane for Twelve-Drive Systems” on page 152
Remove the Storage Drive Backplane for Twenty-
Four Drive Systems
1.
Prepare the server for service.
a.
Power off the server and disconnect the power cords from the power
supplies.
See
“Powering Down the Server” on page 55
.
b.
Extend the server into the maintenance position.
See
“Extend the Server to the Maintenance Position” on page 61
.
c.
Attach an antistatic wrist strap to your wrist, and then to a metal area on the
chassis.
See
“Take Antistatic Measures” on page 64
.
d.
Open the server fan assembly door, and remove the fan modules from the
server.
See
“Remove a Fan Module” on page 89
.
e.
Remove the fan assembly door from the server.
See
“Remove the Fan Assembly Door From the Server” on page 65
.
2.
Pull each storage drive out far enough to disengage it from the disk backplane.
See
“Remove an HDD or SSD Storage Drive” on page 73
.
Note -
It is not necessary to completely remove the storage drives from the server; simply pull
them out far enough to disengage them from the disk backplane. If you do remove the storage
drives from the server, make a note of their locations so that you can reinstall them in the same
locations.
3.
Disconnect the cables from the storage drive backplane.
a.
Disconnect the two power cables and the auxiliary signal cable from the
storage drive backplane [1].
Summary of Contents for X5-2L
Page 1: ...Part No E48333 04 May 2015 Oracle Server X5 2L Service Manual ...
Page 2: ......
Page 12: ...12 Oracle Server X5 2L Service Manual May 2015 ...
Page 24: ...24 Oracle Server X5 2L Service Manual May 2015 ...
Page 50: ...50 Oracle Server X5 2L Service Manual May 2015 ...
Page 70: ...70 Oracle Server X5 2L Service Manual May 2015 ...
Page 100: ...100 Oracle Server X5 2L Service Manual May 2015 ...
Page 268: ...268 Oracle Server X5 2L Service Manual May 2015 ...
Page 292: ...292 Oracle Server X5 2L Service Manual May 2015 ...