Host Link Commands
Section 6-5
Parameters
Name, Word address, Bit (Command)
In “Name,” specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be
forced set. Specify the name in four characters. In “Word address,” specify the
address of the word, and in “Bit” the number of the bit that is to be forced set.
Note
The area specified under “Name” must be in four characters. Add spaces
after the data area name if it is shorter than four characters.
6-5-27 FORCED RESET –– KR
Force resets a bit in the IR, SR, LR, HR, AR, or TC area. Just one bit can be
force reset at a time.
Once a bit has been forced set or reset, that status will be retained until a
FORCED SET/RESET CANCEL (KC) command or the next FORCED SET/
RESET command is transmitted.
Command Format
Response Format
An end code of 00 indicates normal completion.
Parameters
Name, Word address, Bit (Command)
In “Name,” specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be
forced reset. Specify the name in four characters. In “Word address,” specify
the address of the word, and in “Bit,” the number of the bit that is to be forced
reset.
Name
Classification
Word address setting range
Bits
OP1
OP2
OP3
OP4
C
I
O
(Space) IR or SR
0000 to 0252
00 to 15
(decimal)
L
R
(Space) (Space) LR
0000 to 0063
H
R
(Space) (Space) HR
0000 to 0099
A
R
(Space) (Space) AR
0000 to 0027
T
I
M
(Space) Completion Flag (timer)
0000 to 0511
Always 00
T
I
M
H
Completion Flag (high-speed timer)
T
T
I
M
Completion Flag (totalizing timer)
C
N
T
(Space) Completion Flag (counter)
C
N
T
R
Completion Flag (reversible counter)
@
K
R
x 10
0
x 10
1
x 10
3
x 10
2
x 10
1
x 10
0
x 10
1
x 10
0
↵
*
OP1 OP2 OP3 OP4
Node
No.
Header
code
Terminator
FCS
Name
Word
address
Bit
@
K
R
x 10
0
x 10
1
x 16
1
x 16
0
↵
*
Node No.
Header
code
Terminator
FCS
End code