6
PC Setup
Section 1-1
DM 6629
00 to 07
Number of TIMH(15) High-speed Timers to Refresh by Interrupt Refreshing
00 to 15 (BCD; e.g., set 3 for timers 00 to 02)
15
08 to 15
High-speed Timer Interrupt Refresh Enable
00: 16 timers (setting in bits 00 to 07 disabled)
01: Use setting in 00 to 07
DM 6630
00 to 07
First Input Refresh Word for I/O Interrupt 0:
00 to 11 (BCD)
26
08 to 15
Number of Input Refresh Words for I/O Interrupt 0:
00 to 12 (BCD)
DM 6631
00 to 07
First Input Refresh Word for I/O Interrupt 1:
00 to 11 (BCD)
08 to 15
Number of Input Refresh Words for I/O interrupt 1:
00 to 12 (BCD)
DM 6632
00 to 07
First Input Refresh Word for I/O Interrupt 2:
00 to 11 (BCD)
08 to 15
Number of Input Refresh Words for I/O Interrupt 2:
00 to 12 (BCD)
DM 6633
00 to 07
First Input Refresh Word for I/O Interrupt 3:
00 to 11 (BCD)
08 to 15
Number of Input Refresh Words for I/O Interrupt 3:
00 to 12 (BCD)
DM 6634
00 to 07
First Input Refresh Word for High-speed Counter 1:
00 to 11 (BCD)
26
08 to 15
Number of Input Refresh Words for High-speed Counter 1:
00 to 12 (BCD)
DM 6635
00 to 07
First Input Refresh Word for High-speed Counter 2:
00 to 11 (BCD)
26
08 to 15
Number of Input Refresh Words for High-speed Counter 2:
00 to 12 (BCD)
DM 6636
00 to 07
First Input Refresh Word for Interval Timer 0:
00 to 15 (BCD)
32, 39
08 to 15
Number of Input Refresh Words for Interval Timer 0:
00 to 16 (BCD)
DM 6637
00 to 07
First Input Refresh Word for Interval Timer 1:
00 to 15 (BCD)
08 to 15
Number of Input Refresh Words for Interval Timer 1:
00 to 16 (BCD)
DM 6638
00 to 07
First Input Refresh Word for Interval Timer 2 or High-speed Counter 0:
00 to 15 (BCD)
08 to 15
Number of Input Refresh Words for Interval Timer 2 or High-speed Counter 0:
00 to 16 (BCD)
DM 6639
00 to 07
Output Refresh Method
00: Cyclic; 01: Direct
16, 475
08 to 15
Number of Digits for DIGITAL SWITCH (DSW(87)) Instruction
00: 4 digits; 01: 8 digits
16, 427
High-speed Counter Settings (DM 6640 to DM 6644)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6640 to
DM 6641
00 to 15
Inner Board Slot 1 Settings
(See
1-2 Inner Board Settings
for details.)
9
DM 6642
00 to 03
High-speed Counter 0 Input Mode
0: Differential phase mode; 4: Incrementing mode
39
04 to 07
High-speed Counter 0 Reset Mode
0: Phase-Z and software reset; 1: Software reset only
08 to 15
High-speed Counter 0 Enable
00: Don’t use high-speed counter 0; 01: Use high-speed counter 0.
DM 6643 to
DM 6644
00 to 15
Inner Board Slot 2 Settings
(See
1-2 Inner Board Settings
for details.)
9
Word(s)
Bit(s)
Function
Page