background image

Cat. No. I559-E1-01

USER’S MANUAL

SYSDRIVE MX

 SERIES

Multi-function Compact Inverter

Summary of Contents for SYSDRIVE 3G3MX-A2002

Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...

Page 2: ...ith other products You should assume that anything not described in this manual is not possible 2 Although care has been given in documenting the product please contact your OMRON representative if yo...

Page 3: ...After reading this manual keep it handy for future reference z This manual describes the specifications and functions of the product as well as the relations between them You should assume that anyth...

Page 4: ...R USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE OMRON DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED LIMITATIONS OF LIABILITY OMRON SHALL NOT...

Page 5: ...ended to imply that the uses listed may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this...

Page 6: ...t any time to confirm actual specifications of purchased products DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes even when tolerances are s...

Page 7: ...to an electric shock Wiring work must be carried out only by qualified personnel Not doing so may result in a serious injury due to an electric shock Do not put on or take off the Digital Operator co...

Page 8: ...to turn off when unusual overheating is detected in the braking resistor regenerative braking unit The Inverter has high voltage parts inside which if short circuited might cause damage to itself or...

Page 9: ...cover but hold by the fins during transportation Do not connect an AC power supply voltage to the control input output terminals Doing so may result in damage to the product Be sure to tighten the scr...

Page 10: ...try function because the machine may abruptly start when stopped by an alarm Be sure to confirm the RUN signal is turned off before resetting the alarm because the machine may abruptly start Operation...

Page 11: ...9 Precautions for Correct Use Warning Labels Warning labels are located on the Inverter as shown in the following illustration Be sure to follow the instructions Warning Description...

Page 12: ...ecking the Accessories Note that this manual is the only accessory included with the 3G3MX model Mounting screws and other necessary parts must be provided by the user Inverter model Input specificati...

Page 13: ...manual revision code appears as a suffix to the catalog number located at the lower left of the front and back covers Revision code Revision date Changes and revision pages 01 December 2007 First pri...

Page 14: ...s operations including how to use the keys on the Digital Operator and the monitor function Chapter 4 Functions Describes the functions of the Inverter Chapter 5 Maintenance Operations Describes the...

Page 15: ...Wiring 2 10 Chapter 3 Operation 3 1 Test Run Procedure 3 2 3 2 Test Run Operation 3 3 3 3 Part Names and Descriptions of the Digital Operator 3 8 3 4 Operation Procedure Example Factory Default 3 10...

Page 16: ...tents 7 2 Measurement Method of Output Voltage 7 5 7 3 Connection Example 7 6 7 4 Dimensional Drawing 7 8 7 5 Options 7 14 Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...

Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...

Page 18: ...3G3MX A2002 0 4 kW 3G3MX A2004 0 75 kW 3G3MX A2007 1 5 Kw 3G3MX A2015 2 2 kW 3G3MX A2022 3 7 kW 3G3MX A2037 5 5 kW 3G3MX A2055 7 5 kW 3G3MX A2075 3 phase 400 V AC 0 4 kW 3G3MX A4004 0 75 kW 3G3MX A400...

Page 19: ...eceleration Equipped with Communication Function ModBus RTU communication allows you to perform network operation at low cost Easy Operation Adoption of Removable Control Circuit Terminal Block Adopti...

Page 20: ...or and perform wiring to the control circuit terminal block the main circuit terminal block and the relay output terminal block 3G3MX A2002 to A2007 3G3MX AE002 to AE004 Main housing Fin Ground termin...

Page 21: ...r maintenance use only Do not remove the top cover Digital Operator FREQ adjuster Terminal block cover Control circuit wiring hole Main circuit wiring hole Bottom cover Ground terminal Fin Main housin...

Page 22: ...5 to A4075 Digital Operator FREQ adjuster Terminal block cover Control circuit wiring hole Main circuit wiring hole Bottom cover Main housing Fin Front cover Control circuit terminal block A Control c...

Page 23: ...nnector Digital Operator connection plug Digital Operator POWER LED indicator Control circuit terminal block A Main circuit terminal block Relay output terminals Input logic selector ALARM LED indicat...

Page 24: ......

Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...

Page 26: ...mall scale fire heat generation or damage to the unit Install a stop motion device to ensure safety Not doing so might result in a minor injury A holding brake is not a stop motion device designed to...

Page 27: ...tion and Wiring Do not drop or apply strong impact on the product Doing so may result in damaged parts or malfunction Do not hold by the terminal cover but hold by the fins during transportation Do no...

Page 28: ...er supply voltage Precautions for Use Position for installing a screw Position for installing a screw Model 3G3MX A2002 A2004 A2007 AE002 AE004 Screw size for installation M5 Positions for installing...

Page 29: ...n into consideration If the ambient temperature is from 40 C to 50 C the carrier frequency should be reduced and the Inverter capacity should be increased Before installing the Inverter place a cover...

Page 30: ...37 3G3MX AE002 to AE022 1 Removing the Terminal Block Cover Press the one side 1 of tab A on the terminal block cover and use the opposite side of tab A as a supporting point to disconnect tab B on th...

Page 31: ...into place 3G3MX A2055 to A2075 3G3MX A4055 to A4075 1 Removing the Terminal Block Cover Press the two A tabs on the terminal block cover toward the direction of the arrow in the figure below and unl...

Page 32: ...abs click into place Removing and Mounting the Digital Operator Removing the Digital Operator Pressing the upper tab on the Digital Operator pull it up to the Inverter s front upper direction in the f...

Page 33: ...b into the communication connector until it clicks into place Removing and Mounting the Control Circuit Terminal Blocks Removing the Control Circuit Terminal Blocks Step 1 Pull up control circuit term...

Page 34: ...Push control circuit terminal block B Terminals FS FV FI FC AM PC P2 P1 down securely from the Inverter s bottom right lower direction in the figure on the previous page Furthermore securely tighten...

Page 35: ...ses 3G3MX A2015 to A2037 3G3MX A4004 to A4037 3G3MX AE007 to AE022 Terminal symbols for 3G3MX AE are indicated in parentheses RB 1 R L1 L1 S L2 L2 T L3 N L3 Upper Lower Short circuit bar P 2 N U T1 V...

Page 36: ...V Frequency reference 1 to 2 k Frequency reference input voltage Frequency reference input current 4 to 20 mA 1 Terminal symbols for 3G3MX AE are indicated in parentheses 2 Connect a single phase 200...

Page 37: ...the motor is too long longer than 10 m the thermal relay may malfunction due to harmonics Install an AC reactor on the Inverter output side or use a current sensor instead of the thermal relay Note 2...

Page 38: ...rminal block A SC S6 S5 S4 S3 S2 S1 PSC FS FC AM PC P1 P2 MB Relay Relay output Relay output terminal block Control circuit terminal block B FV FI MA MC Input common SC S6 S5 S4 S3 S2 S1 PSC FS FC AM...

Page 39: ...connection is not required Connect to the ground terminal of the Inverter Perform insulating treatment Inverter s internal circuitry When interface power supply is used When external power supply is...

Page 40: ...tube mounted cable and multi core cable keep both the mark tube and the sheath stripped length 40 mm or more from the connecting end A thick line may prevent proper closing of the cover of the termina...

Page 41: ...el higher The leakage current mentioned here is the effective value of the fundamental wave and high frequency currents are excluded 100 m max 30 300 m max 100 800 m max 200 Main circuit terminal bloc...

Page 42: ...e input power supply Do not remove the short circuit bar between 1 and P 2 when a DC reactor is not connected U T1 V T2 W T3 Inverter output terminal Connect to the motor 1 P 2 External DC reactor ter...

Page 43: ...ecial purpose ground fault interrupter for Inverters that exclude high frequency leakage current and detect only the leakage current within a frequency range that is hazardous to humans Choose a groun...

Page 44: ...leration this indicates that the regenerative energy exceeds the capacity of the Inverter In this case use a regenerative braking unit When using a regenerative braking unit be sure to include a seque...

Page 45: ...nimize noise transmission Installing a noise filter on the input side can also reduce the noise from the power line to the Inverter Recommended Input Noise Filters for the Inverter Use a noise filter...

Page 46: ...reful not to short circuit the output wires Do Not Use a Phase Advance Capacitor or Noise Filter Doing so may result in damage to the Inverter or cause the parts to burn Never connect a phase advance...

Page 47: ...Inverter s output unit and peripheral devices If your system configuration requires a cable length of 50 m or more perform the following Wire in metallic ducts Use separate cables for each phase Set...

Page 48: ...e 1 S6 Multi stepspeed reference 2 SC Input signal common Monitor signal AM Analog frequency monitor Analog output current monitor Analog frequency monitor SC Monitor common Frequency reference input...

Page 49: ...lied with the Inverter it is available regardless of the switch condition Output terminal Resistance load Inductive load MA MC Max contact capacity 250 V AC 2 A 30 V DC 3 A 250 V AC 0 2 A 30 V DC 0 6...

Page 50: ...values in A001 and A002 are disabled Frequency reference Analog external input FV FI RUN command Operation using the FW or RV terminal 00 FW or 01 RV must be allocated to the multi function input term...

Page 51: ...input terminal has no allocation of 16 AT the frequency of total voltage and current directive values will be output When selecting and using either the voltage or current be sure to allocate 16 AT to...

Page 52: ...eck the contact logic of the relay output terminal setting C036 and match the logic with that of the peripheral circuit before use If these contact logics conflict with each other a system breakdown m...

Page 53: ...to the option connected to the communications connector 2 485 ModBus communication OPE factory default Digital Operator Option 3G3AX OP01 TM PRG Frequency reference RUN command source selector Switch...

Page 54: ...L1 S L2 and T L3 and power supply via an EMC conforming dedicated noise filter 3G3AX EFI Keep the ground cable as short as possible Keep the cable between the Inverter and the noise filter as short as...

Page 55: ...t Run Procedure 3 2 3 2 Test Run Operation 3 3 3 3 Part Names and Descriptions of the Digital Operator 3 8 3 4 Operation Procedure Example Factory Default 3 10 3 5 Keys 3 16 3 6 Parameter Transition 3...

Page 56: ...gital Operator control circuit terminal block terminal block cover while the input power is being supplied Doing so may result in a serious injury due to an electric shock Do not remove the terminal b...

Page 57: ...splays the set value in d001 If an error occurs the error code is displayed on the data display In this case refer to Chapter 5 Maintenance Operations and make the necessary changes to remedy Set para...

Page 58: ...turned off Set the motor to a no load state i e not connected to the mechanical system Power On After checking the above turn on the power Display Status Check When the power is turned on normally th...

Page 59: ...crement or Decrement key to display b084 Press the Mode key The set value in b084 is displayed Use the Increment or Decrement key to display 02 Press the Enter key The set value is entered and b084 is...

Page 60: ...election Sets the pole number of the motor connected to the Inverter 2 4 6 8 Pole 4 No H007 Motor voltage selection Sets the voltage of the motor connected to the Inverter 00 200 V 01 400 V Depends on...

Page 61: ...otor in the no load status connect the mechanical system and operate with an actual load Before operating the Digital Operator check that the FREQ adjuster is set to MIN Connecting the Mechanical Syst...

Page 62: ...is correct and that the Inverter is operating smoothly at a slow speed increase the frequency reference By changing the frequency reference or the rotation direction make sure that there is no vibrat...

Page 63: ...uency A Current Volume LED indicator Lit when the frequency reference source is set to the FREQ adjuster FREQ adjuster Sets a frequency Available only when the frequency reference source is set to the...

Page 64: ...eration Enter key Enters the set value To change the set value be sure to press the Enter key Increment key Changes the mode Also increases the set value of each function Decrement key Changes the mod...

Page 65: ...and Extended Function Mode 1 The data of the set monitor is displayed Default is 0 0 2 The code of the monitor mode is displayed as d001 Press the Mode key once to return from the code display of the...

Page 66: ...ic function mode is displayed as F001 4 The extended function mode is displayed as A Extended function mode Displays in order of A b C H 5 The code of the monitor mode is displayed as d001 Returns to...

Page 67: ...w the indication method described in Displaying the Monitor Mode Basic Function Mode and Extended Function Mode page 3 10 By default the RUN command LED indicator will light up as the RUN command sour...

Page 68: ...the control terminal 01 4 The code of the monitor mode is displayed as A002 Press the Enter key to fix the changed setting data The RUN command source is changed to the control terminal and the RUN c...

Page 69: ...rd digit of the function code 0 of the 3rd digit blinks Press the Enter key to fix 0 of the 3rd digit as you need not change it Press the Mode key to start A blinking again 4 Change the 2nd digit of t...

Page 70: ...f the 1st digit blinks 6 The function code selection is complete A029 selection completed Press the Mode key to change the data for A029 Supplemental Information If you enter a parameter number that i...

Page 71: ...n the Mode key for 3 seconds Note Always press the Enter key to store any changed data Increment key Changes the set values parameters and commands Decrement key RUN key Starts the operation Forward R...

Page 72: ...s selected 4 When you press the Enter key with d or F001 displayed the monitor value is stored as the initial display that appears when the power is turned on 5 When you press the Enter key the first...

Page 73: ...ress the Enter key with that monitor displayed If a parameter for an extended function code is stored after pressing the Enter key however that code A b C d or H appears at the next power on To preven...

Page 74: ...OFF 4 2 d007 Output frequency monitor after conversion 0 00 to 99 99 100 0 to 999 9 1000 to 9999 1000 to 3996 10000 to 39960 Output frequency Conversion factor of b086 4 2 d013 Output voltage monitor...

Page 75: ...99 99 100 0 to 999 9 1000 to 3000 10 0 Yes s 4 5 F203 2nd deceleration time 1 0 01 to 99 99 100 0 to 999 9 1000 to 3000 10 0 Yes s 4 5 F004 Operator rotation direction selection 00 Forward 01 Reverse...

Page 76: ...frequency A004 60 No Hz 4 8 A203 2nd base frequency 30 to Max frequency A204 60 A004 Maximum frequency 30 to 400 60 No Hz 4 9 A204 2nd maximum frequency 60 Analog input A005 FV FI selection 00 Switch...

Page 77: ...step speed reference 7 0 0 A028 Multi step speed reference 8 0 0 A029 Multi step speed reference 9 0 0 A030 Multi step speed reference 10 0 0 A031 Multi step speed reference 11 0 0 A032 Multi step spe...

Page 78: ...No 4 12 A244 2nd V f characteristics selection 00 A045 Output voltage gain 20 to 100 100 Yes 4 12 4 34 4 63 A245 2nd output voltage gain 100 4 12 A046 Automatic torque boost voltage compensation gain...

Page 79: ...0 0 No Hz 4 17 A261 2nd frequency upper limit 0 0 Frequency lower limit to 2nd Max frequency 0 0 A062 Frequency lower limit 0 0 Starting frequency to Frequency upper limit 0 0 No Hz 4 17 A262 2nd freq...

Page 80: ...ID function 00 OFF Deviation Target value Feedback value 01 ON Deviation Feedback value Target value 00 No 4 18 A078 PID output limit function 0 00 to 100 0 0 0 No 4 18 AVR A081 AVR selection 00 Alway...

Page 81: ...ration frequency 0 0 A096 2 step deceleration frequency 0 0 to 400 0 0 0 No Hz 4 22 A296 2nd 2 step deceleration frequency 0 0 A097 Acceleration pattern selection 00 Line 01 S shape curve 00 No 4 23 A...

Page 82: ...A153 VR start ratio 0 to 100 0 No 4 10 A154 VR end ratio 0 to 100 100 No 4 10 A155 VR start selection 00 Use start frequency A151 01 0 Hz start 01 No 4 10 Restart after momentary power interruption b0...

Page 83: ...29 b223 2nd overload limit parameter 1 0 b028 Overload limit source selection 00 b022 b222 set values 01 Input terminal FV 00 No 4 29 b228 2nd overload limit source selection 00 Lock b031 Soft lock se...

Page 84: ...95 Regenerative braking function operation selection 00 Disabled 01 Enable Disable during stop 02 Enable Enable during stop 0 0 No 4 37 b096 Regenerative braking function ON level 200 V class 330 to 3...

Page 85: ...pecial setting 255 No function 00 No 4 41 C201 2ndmulti function input 1 selection 00 C002 Multi function input 2 selection 01 C202 2ndmulti function input 2 selection 01 C003 Multi function input 3 s...

Page 86: ...tact at MA NC contact at MB 01 NC contact at MA NO contact at MB 00 No 4 60 C032 Multi function output terminal P2 contact selection 00 C036 Relay output MA MB contact selection 01 Level output status...

Page 87: ...ore 03 Free run 04 Deceleration stop 02 No 4 66 C077 Communication error timeout 0 00 to 99 99 0 00 No s 4 66 C078 Communication wait time 0 to 1000 0 No ms 4 66 Various adjustment C081 FV adjustment...

Page 88: ...ID FB value fault 08 NDc network error 10 ODC communication option disconnected 00 No 4 59 C142 Logic operation function B input 01 No 4 59 C143 Logic operator selection 00 AND 01 OR 02 XOR 00 No 4 59...

Page 89: ...No Pole 4 63 H204 2nd motor pole number selection 4 H006 Stabilization parameter 0 to 255 100 Yes 4 34 4 63 H206 2nd stabilization parameter 100 H007 Motor voltage selection 00 200 V 01 400 V Factory...

Page 90: ......

Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...

Page 92: ...in increments of 0 1 A Rotation Direction Monitor d003 Displays whether the Inverter output is in a forward reverse stop status The RUN LED indicator lights up during forward reverse rotation Display...

Page 93: ...t set in b086 Displayed value Output frequency d001 Frequency conversion coefficient b086 Display d007 0 00 to 99 99 Displays in increments of 0 01 100 0 to 999 9 Displays in increments of 0 1 1000 to...

Page 94: ...hour 1000 to 999 Displays in increments of 10 hours 100 to 999 Displays in increments of 1000 hours Fault Frequency Monitor d080 Displays the number of times the Inverter has tripped Display 0 to 9999...

Page 95: ...unctions Trip Monitor Display Sequence 2 Displays if there has been no trip 1 Trip factor 2 2 Trip frequency 3 Trip current 4 Trip P N voltage 5 Total RUN time 6 Power ON time dk0k8k1 ekLk0k7 6k0 0 4...

Page 96: ...the 2nd multi step speed allocate 08 SET to the multi function input and then turn it on Acceleration Deceleration Time Set an acceleration deceleration time for the motor For a slow transition set t...

Page 97: ...direction of motor rotation applied to the RUN command via the Digital Operator This is disabled at terminals Parameter No Function name Data Default setting Unit F004 Operator rotation direction sel...

Page 98: ...ncy reference allocate 08 SET to the multi function input and then turn it on Parameter No Function name Data Default setting Unit A001 Frequency reference selection 00 Digital Operator FREQ adjuster...

Page 99: ...tive from the terminal 02 F001 value set via the Digital Operator 03 ModBus communication 10 Result of the frequency operation function Parameter No Function name Data Default setting Unit A002 RUN co...

Page 100: ...0 V in the range from 0 to 10 V of the external analog input frequency reference The maximum Inverter output voltage from base to maximum frequencies is the voltage set in AVR voltage selection A082 T...

Page 101: ...FREQ adjuster on the Digital Operator Parameter No Function name Data Default setting Unit A005 FV FI selection 00 Switches between FV FI via terminal AT 01 Operation via terminal AT is disabled 02 Sw...

Page 102: ...ion Between Torque Boost and V f Characteristics Determine the relation of output voltage against output frequency Related functions A005 A016 AT input Parameter No Function name Data Default setting...

Page 103: ...tant torque characteristics within a range from 0 to 6 Hz Period b Provides reduced torque characteristics within a range from 10 to 100 of the base frequency The Inverter outputs voltage based on a c...

Page 104: ...e obtained if you select two or more lower rank motor size than specified 0 Output voltage 100 Manual torque boost voltage A042 A242 Manual torque boost frequency A043 A243 Base frequency A003 A203 Ma...

Page 105: ...hes the specified level during operation If DC injection braking operates at a high motor speed an overcurrent trip E01 to E04 or overload trip E05 may occur For internal DC injection braking the foll...

Page 106: ...otor goes into free run status After the set time elapses DC injection braking starts Set the DC injection braking time A055 via the Digital Operator or the DB terminal while taking into account motor...

Page 107: ...elapses Below are edge level operations in internal DC injection braking Edge operation Giving priority to the DC injection braking time A055 performs DC injection braking for the specified period DC...

Page 108: ...the set value is prioritized even if 0 V 4 mA is input for frequency reference Example 6 a Example 6 b FW Output frequency A052 A055 FW Output frequency A052 A055 Parameter No Function name Data Defa...

Page 109: ...ncy 1 Jump frequency 2 Jump frequency 3 0 0 to 400 0 0 0 Hz A064 A066 A068 Jump frequency width 1 Jump frequency width 2 Jump frequency width 3 0 0 to 10 0 0 5 Related functions C001 to C006 Output fr...

Page 110: ...ration where the control volume is proportional to the target value I Operation Operation where the control volume increases linearly according to time C044 PID deviation excessive level 0 to 100 3 0...

Page 111: ...ID deviation excessive level C044 during PID control If the PID deviation reaches the PID deviation excessive level C044 the multi function output terminal is turned on C044 can be set from 0 to 100 T...

Page 112: ...based on that set in the motor voltage selection With A081 AVR selection set whether to enable or disable this function Note that the Inverter cannot output voltage beyond that of the incoming voltage...

Page 113: ...0 15 0 s A293 2nd deceleration time 2 15 0 s A094 2 step acceleration deceleration selection 00 Switched via multi function input 09 2CH 01 Switched by setting 00 A294 2nd 2 step acceleration decelera...

Page 114: ...rve 00 A098 Deceleration pattern selection 00 Line 01 S shape curve 00 Parameter No Set value 00 01 Line S shape A097 Acceleration A098 Deceleration Description Accelerates Decelerates linearly before...

Page 115: ...Result of calculation Output frequency A142 Digital Operator FREQ adjuster Input FV Input FI ModBus communication Parameter No Function name Data Default setting Unit A145 Frequency addition amount 0...

Page 116: ...interruption and undervoltage if b005 is set to 01 the retry operation continues until the status is cleared You can select the operation for momentary power interruption and undervoltage during stop...

Page 117: ...y power interruption t1 Allowable duration of momentary power interruption b002 t2 Retry wait time b003 Power supply Inverter output Motor rotation speed Alarm ON OFF Free running t0 t1 Example 1 Dura...

Page 118: ...6 0 A The following figure shows the time limit characteristics with the electronic thermal level b012 set to 5 0 A Electronic Thermal Characteristics Frequency characteristics are multiplied by the b...

Page 119: ...er output frequency Hz Example 3G3MX A2007 Rated current 5 0 A b012 5 00 A Output frequency 20 Hz Trip time s Motor current A Ratio to the rated current of the Inverter 60 4 0 4 64 92 8 6 0 120 8 0 16...

Page 120: ...leration from this function even during acceleration Make the following adjustments if this function operates during acceleration and the frequency doesn t reach the target level Increase the accelera...

Page 121: ...47 This helps prevent data rewriting due to erroneous operation Select the soft lock setting and performing method from the above table When using the multi function input allocate 15 SFT to it Overlo...

Page 122: ...torque With the starting frequency set high the starting current increases Therefore the current may exceed the overload limit and cause an overcurrent trip Parameter No Function name Data Default se...

Page 123: ...when the ambient temperature is 40 C Parameter Initialization You can initialize the rewritten set values and reset to the factory default or clear trip records Note that this is not available for RUN...

Page 124: ...so initialized with this function To avoid unexpected opera tion be sure to re examine the wiring 1 Press the STOP RESET key with the Mode and Increment Decrement keys pressed simultaneously Release t...

Page 125: ...djust the FV FI frequency input Use this to change the full scale of input The set frequency becomes 0 Hz with 0 0 set This returns to the factory default value after initialization Parameter No Funct...

Page 126: ...lection You can select whether to enable the STOP key on the Digital Operator even if the RUN command is set to the control terminal block terminal The trip reset function via the STOP RESET key works...

Page 127: ...nction applies to the Inverter models with a built in cooling fan Example 1 0 Hz start FW FRS Motor rotation speed 0 Free running 0 Hz start Example 2 Frequency matching start FW FRS Motor rotation sp...

Page 128: ...disable the regenerative braking function selection b095 00 Do not mount the braking resistor between terminals P 2 and RB Parameter No Function name Data Default setting Unit b090 Usage rate of rege...

Page 129: ...esumes if the voltage level falls below the overvoltage LAD stop level With the overvoltage LAD stop function enabled b130 01 the actual deceleration time becomes longer than the set value F003 F203 T...

Page 130: ...equency when the temperature of the semiconductor inside the Inverter becomes high While this function is activated the noise from the motor may be heard differently because of automatic change in car...

Page 131: ...data other than the parameters changeable during operation cannot be changed Group C Multi function Terminal Function The 3G3MX has six multi function inputs S1 S2 S3 S4 S5 and S6 two open collector...

Page 132: ...P 3 wire stop 22 F R 3 wire forward reverse 23 PID PID enabled disabled 24 PIDC PID integral reset 27 UP UP DWN function accelerated 28 DWN UP DWN function decelerated 29 UDC UP DWN function data clea...

Page 133: ...OFF e g if 02 CF1 and 03 CF2 are allocated to multi function inputs the available multi step speeds are 0 to 3 For speed 0 you can change the frequency reference with the frequency reference selection...

Page 134: ...10th ON OFF 11th ON 12th ON OFF OFF 13th ON 14th ON OFF 15th ON CF1 CF2 CF3 CF4 FW 1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th 11th 12th 13th 14th 15th 0th Frequency reference from the Digital Operator...

Page 135: ...ction This function is used to operate by switching two different types of motors By allocating 08 SET or 53 SP SET to the desired multi function input and then turning on off the SET or SP SET termin...

Page 136: ...A042 A242 Manual torque boost voltage Yes Yes A043 A243 Manual torque boost frequency Yes Yes A044 A244 V f characteristics selection No Yes A045 A245 Output voltage gain No Yes A046 A246 Automatic t...

Page 137: ...put 1 selection No Yes C002 C202 Multi function input 2 selection No Yes C003 C203 Multi function input 3 selection No Yes C004 C204 Multi function input 4 selection No Yes C005 C205 Multi function in...

Page 138: ...g shows how this function works Soft Lock Function Use this function to prohibit rewriting of each parameter This helps prevent data rewriting due to erroneous operation Allocate 15 SFT to the desired...

Page 139: ...he Inverter is running Cleared at trip The same process as when the power is turned on OFF Same as above Available input terminals C001 C002 C003 C004 C005 C006 Required settings C102 Parameter No Fun...

Page 140: ...minals are disabled Below are the outputs via terminal operation Data Symbol Function name Status Description 20 STA 3 wire start ON Starts with auto recovery contacts OFF Irrelevant to the motor oper...

Page 141: ...ases the current speed during the signal input period OFF Keeps the current speed 29 UDC UP DWN function data clear ON Clears the stored UP DWN speed OFF Keeps the stored UP DWN speed Available input...

Page 142: ...uency RUN commands FW and RV UP DWN Output frequency Acceleration Deceleration does not function if the UP and DWN terminals are turned on simultaneously Data Symbol Function name Status Description 3...

Page 143: ...time through this function varies depending on timing When the Inverter is in ready status high voltage is applied to terminals U V and W on the main circuit terminal block This happens even if the mo...

Page 144: ...etwork error 09 LOG logic operation output 10 ODc communication option disconnected 00 C022 Multi function output terminal P2 selection 01 C026 Relay output MA MB function selection 05 Data Descriptio...

Page 145: ...frequency has fallen below the F001 set value 02 FA2 Over set frequency arrival signal ON The Inverter output frequency has exceeded the C042 set value during acceleration OFF The Inverter output fre...

Page 146: ...d trip of the Inverter C042 f on f off C043 f on 1 of max frequency f off 2 of max frequency Output frequency FA2 Data Symbol Function name Status Description 03 OL Overload warning ON The Inverter ou...

Page 147: ...the terminals For details refer to the description of the relay output Multi function Output Terminal ON Delay OFF Delay page 4 60 Data Symbol Function name Status Description 04 OD Excessive PID dev...

Page 148: ...ion even when the frequency reference is set to the external analog input A001 01 Example 2 Disabled even when the FV FI selection is set to the FV VR selection A005 02 or FI VR selection A005 03 sinc...

Page 149: ...Data Symbol Function name Status Description 07 FBV PID FB status output ON See the figure below Shifts output when exceeding the upper limit or falling below the lower limit OFF Available input termi...

Page 150: ...cified time period Data Symbol Function name Status Description 09 LOG Logic operation output ON See the figure below OFF Available input terminals P1 PC P2 PC MA MC or MB MC Required settings C021 C0...

Page 151: ...DT contact relay output Parameter No Function name Data Default setting Unit C144 Output terminal P1 ON delay 0 0 to 100 0 0 0 s C145 Output terminal P1 OFF delay 0 0 to 100 0 0 0 s C146 Output termin...

Page 152: ...50 mA OFF OFF 01 NC contact ON ON OFF OFF Electrical specifications Output terminal Resistance load Inductive load MA MC Max contact capacity 250 V AC 2 A 30 V DC 3 A 250 V AC 0 2 A 30 V DC 0 6 A Min...

Page 153: ...onnected to the AM terminal by using the Inverter setting a AM adjustment value change Parameter No Function name Data Default setting Unit C028 AM selection 00 Output frequency 0 to 10 V 0 to Max fre...

Page 154: ...lower the manual torque boost voltage A042 A242 and manual torque boost frequency A043 A243 Other than this function the following methods are suggested to reduce hunting Lower the carrier frequency b...

Page 155: ...r plug mounted in the communication connector 4 Insert the communication cable connected to the ModBus bus line 5 Set the 485 OPE communications selector to 485 Function name Description Note Transmis...

Page 156: ...tion example where the external controller master incorporates a termination resistor Pin No Symbol Description 1 Not used Do not connect 2 Not used Do not connect 3 Not used Do not connect 4 Not used...

Page 157: ...the Inverter to the external control device Response The Inverter returns a response Frame 2 only after receiving a query Frame 1 and does not output a response positively Below is each frame format...

Page 158: ...heck is used for the Modbus RTU error check The CRC code is 16 bit data generated for the block of random length data in the 8 bit unit To prepare the CRC code use a generation polynomial of CRC 16 X1...

Page 159: ...om the Inverter be sure to provide the silent interval length 3 5 character length or more at the minimum Normal Response If the query is the loopback function code 08h the Inverter sends back a respo...

Page 160: ...to monitor the response and if no response is returned within the set time period send the same query again Explanation of Each Function Code Reading Coil Status 01h Reads out the coil status ON OFF...

Page 161: ...s the specified number of consecutive holding register contents from the specified holding reg ister addresses Example Read the factors on the past three trips from the Inverter with slave address 5 B...

Page 162: ...se No Field name Example HEX No Field name Example HEX 1 Slave address 1 05 1 Slave address 05 2 Function code 03 2 Function code 03 3 Register start number MSB 00 3 Number of data bytes 2 06 4 Regist...

Page 163: ...etween master and slave A random value can be used for test data Query Response No Field name Example HEX No Field name Example HEX 1 Slave address 0 A 1 Slave address 0 A 2 Function code 05 2 Functio...

Page 164: ...00 3 Diagnostic sub code MSB 00 4 Diagnostic sub code LSB 00 4 Diagnostic sub code LSB 00 5 Data MSB Random 5 Data MSB Random 6 Data LSB Random 6 Data LSB Random 7 CRC 16 MSB CRC 7 CRC 16 MSB CRC 8 C...

Page 165: ...tes to be changed not the number of holding registers Refer to Exception Response below if writing into the multiple holding register cannot be per formed normally Exception Response The master requir...

Page 166: ...er 0900h using the writing command into the holding register 06h In this case a random value can be written into the holding register Notes The Enter command needs considerable time Monitor the data w...

Page 167: ...input 5 R W 1 ON 0 OFF 1 000Ch Multi function input 6 R W 1 ON 0 OFF 1 000Dh Not used 000Eh Operation status R 1 RUN 0 Stop Interlocked with d003 000Fh Rotation direction R 1 Reverse 0 Forward Interl...

Page 168: ...put terminals If the master cannot reset the coil ON status because of communication disconnection turn the control circuit terminal block from ON to OFF in order to turn off the coil 2 The content of...

Page 169: ...0 to 65535 0019h Fault monitor 1 d081 R Indicates the cause of the trip 001Ah Fault monitor 2 d082 R Indicates the cause of the trip 001Bh Fault monitor 3 d083 R Indicates the cause of the trip 001Ch...

Page 170: ...0036h FV start ratio A013 R W 0 to 100 1 0037h FV end ratio A014 R W 0 to 100 1 0038h FV start selection A015 R W 0 External start frequency 1 0 Hz 0039h FV FI sampling A016 R W 1 to 8 1 003Ah Multi...

Page 171: ...requency 0 1 Hz 004Bh Jogging frequency A038 R W 0 Starting frequency to 999 0 01 Hz 004Ch Jogging stop selection A039 R W 0 Free run stop 1 Deceleration stop 2 DC injection braking stop 004Fh Manual...

Page 172: ...to Frequency upper limit 0 1 Hz 0065h 2nd frequency lower limit A262 R W 0 Starting frequency to 2nd frequency upper limit 0 1 Hz 0066h Jump frequency 1 A063 R W 0 to 4000 0 1 Hz 0067h Jump frequency...

Page 173: ...ion A094 R W 0 Switched via terminal 2CH 1 Switched by setting 007Dh 2nd 2 step acceleration deceleration selection A294 R W 0 Switched via terminal 2CH 1 Switched by setting 007Eh 2 step acceleration...

Page 174: ...acteristics selection b013 R W 0 Reduced torque characteristics 1 1 Constant torque characteristics 2 Reduced torque characteristics 2 1 0091h 2nd electronic thermal characteristics selection b213 R W...

Page 175: ...function b090 R W 0 to 1000 0 1 00A0h Stop selection b091 R W 0 Deceleration Stop 1 Free run stop 00A1h Cooling fan control b092 R W 0 Always ON 1 ON only during RUN including 5 minutes after power o...

Page 176: ...C005 R W 00ACh Multi function input 6 selection C006 R W 00ADh Multi function input 1 operation selection C011 R W 0 NO 1 NC 00AEh Multi function input 2 operation selection C012 R W 0 NO 1 NC 00AFh...

Page 177: ...000 0 1 00C0h Not used 00C1h Not used 00C2h Not used 00C3h Not used 00C4h Not used 00C5h Not used 00C6h Not used 00C7h FV adjustment C081 R W 0 to 2000 0 1 00C8h FI adjustment C082 R W 0 to 2000 0 1 0...

Page 178: ...0000 100 0 seconds Register No Function name Parameter No R W Data Data resolution 0100h Fault monitor 1 d081 R Trip monitor 1 Factor code 0101h R Trip monitor 1 Frequency 0 1 Hz 0102h R Trip monitor...

Page 179: ...e 0 1 V 0114h R Trip monitor 3 Run time H 1 h 0115h R Trip monitor 3 Run time L 0116h R Trip monitor 3 ON time H 1 h 0117h R Trip monitor 3 ON time L 0900h Write all memory data W Indefinite value Reg...

Page 180: ......

Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...

Page 182: ...hen the voltage on the converter exceeds the specified level EEPROM error 2 3 Shuts off the output if an error occurs in the EEPROM built into the Inverter due to external noise and abnormal temperatu...

Page 183: ...reset input Shut off the power and check the wiring 6 If the multi function output relay output is set to 05 alarm the signal may not be output during the CPU error In this case no error data is store...

Page 184: ...y condition or with the power shut off Restart during momentary power interruption Restart during trip Restart function is in operation Setting initialization Appears while the set values are being in...

Page 185: ...when the trip occurred LkLk4 0 3 Output current A when the trip occurred Lk3k9k8 4 DC voltage V between P and N when the trip occurred LkLk1k5 5 Total RUN time before the trip LkLk1k8 6 Total power ON...

Page 186: ...W or RV input and terminal SC or PSC connected Is the SK SR selector status correct Check the terminal allocation C001 to C006 Turn on the RUN key RUN command Connect FW or RV input to terminal SC or...

Page 187: ...correct Check the V F pattern according to the motor specifications Check the transmission gear ratio Data value is abnormal Does not change with data set After changing the data using the Increment D...

Page 188: ......

Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...

Page 190: ...f the product Do not put on or take off the Digital Operator control circuit terminal block terminal block cover while the input power is being supplied Doing so may result in a serious injury due to...

Page 191: ...PCB cables Doing so may result in fire or injury due to cable damage Inspection Item Daily inspection Periodic inspection about every year Insulation resistance test about every two years Megger test...

Page 192: ...t humidity 20 to 90 With no condensation Thermometer Hygrometer Entire device Check that there are no abnormal vibrations or sounds 3 Visual or acoustic inspection Powersupply voltage Check that the m...

Page 193: ...lay terminal block Check that there is no abnormal sound during operation 3 Acoustic inspection No faults Resistor Check that there are no large fissures or discoloration in the resistance insulation...

Page 194: ...eral Check that there are no abnormal odors or discoloration Check that there is no significant rusting 3 3 Visual inspection No faults Capacitor Check that there is no liquid leakage or deformation 3...

Page 195: ...rter Measurement item Measurement point Measurement device Note Measurement value reference Power supply voltage EI Phase to phase voltage between R S S T and T R ER ES ET Moving iron voltmeter or Rec...

Page 196: ...Inverter temporarily for transportation Storage temperature 10 C to 60 C Humidity 20 to 90 RH Without condensation or freezing due to rapid temperature change Do not store this unit in a place with du...

Page 197: ...Chapter 7 Specifications 7 1 Standard Specification List 7 1 7 2 Measurement Method of Output Voltage 7 5 7 3 Connection Example 7 6 7 4 Dimensional Drawing 7 8 7 5 Options 7 14...

Page 198: ...eration 3 At capacitor feedback Approx 50 Approx 20 to 40 Approx 20 For mounting discharge resistance Approx 150 Approx 100 Approx 80 Minimumconnection resistance 100 100 50 50 35 35 17 17 Item 3 phas...

Page 199: ...l Method Phase to phase sinusoidal modulation PWM Output frequency range 5 0 5 to 400 Hz Frequency precision 6 Digital command 0 01 of the max frequency Analog command 0 2 of the max frequency 25 C 10...

Page 200: ...WN function decelerated PID PID enabled disabled PIDC PID deviation clear PTC thermistor input UDC UP DWN function data clear SFT soft lock ADD frequency addition F TM forced terminal block RDY operat...

Page 201: ...To operate the motor at over 50 60 Hz contact the motor manufacturer to find out the maximum allowable revolution 6 For the stable control of the motor the output frequency may exceed the maximum freq...

Page 202: ...e Terminal symbols for 3G3MX AE are indicated as L1 L2 N L3 instead of R L1 S L2 T L3 respecitively Measurement Method of Output Voltage R L1 S L2 T L3 U T1 V T2 W T3 Motor Diode 600 V 0 01 A min 200...

Page 203: ...quency setting unit 1 to 2 k Power supply input 4 to 20 mA DC 24 V DC 250 FS FV FI FC 10 k DC 10 V S5 4 7 k MB MA MC Relay output terminals R L1 L1 7 S L2 L2 T L3 N L3 MC ELB 3 phase AC T 3 U T1 V T2...

Page 204: ...re 5 If the main circuit is turned on at the same time as a RUN command is input the motor begins to rotate at least 2 0 seconds later Secure a duty cycle of 5 minutes or more between switching the po...

Page 205: ...7 8 7 4 Dimensional Drawing 7 Specifications 7 4 Dimensional Drawing 3G3MX A2002 AE002 120 110 67 5 6 5 103 2 6 7 80...

Page 206: ...7 9 7 4 Dimensional Drawing 7 Specifications 3G3MX A2004 AE004 MIN MAX 3G3MX INVERTER STOP RESET Hz RUN POWER ALARM A PRG RUN SYSDRIVE 5 5 67 6 110 7 117 2 6 120...

Page 207: ...7 10 7 4 Dimensional Drawing 7 Specifications 3G3MX A2007 5 67 5 6 110 7 140 2 6 120 MIN MAX 3G3MX INVERTER STOP RESET Hz RUN POWER ALARM A PRG RUN SYSDRIVE...

Page 208: ...7 11 7 4 Dimensional Drawing 7 Specifications 3G3MX A4004 AE007 139 2 6 7 98 118 4 130 2 5 110 5...

Page 209: ...7 12 7 4 Dimensional Drawing 7 Specifications 3G3MX A2015 A2022 A2037 A4007 A4015 A4022 A4037 AE015 AE022 118 98 110 5 2 5 4 166 6 7 130...

Page 210: ...7 13 7 4 Dimensional Drawing 7 Specifications 3G3MX A2055 A2075 A4055 A4075 205 220 6 5 6 164 180 2 6 7 155 5 5...

Page 211: ...7 14 7 5 Options 7 Specifications 7 5 Options Regenerative Braking Unit 3G3AX RBU Series Dimensional Drawing 3G3AX RBU21 RBU22 95 5 100 35 145 5 208 218 75 2 5...

Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...

Page 213: ...F for 40 s Cycle 1 10 ON for 10 s OFF for 90 s Power consumption Instantaneous 0 73 kW Short time rating 120 W Instantaneous 6 kW Short time rating 120 W Instantaneous 0 73 kW Rating 120 W 2 in series...

Page 214: ...1 Resistance Capacity 120 W 120 W 120 W 120 W 200 W 200 W 300 W 400 W Resistance 100 100 50 35 100 100 50 35 Allowable braking frequency 5 2 5 15 10 10 75 7 5 7 Continuous allowable braking time s 20...

Page 215: ...icable wire W D H B X Y C K 3 1 phase 200 V AC 3G3AX DL2002 Fig 1 0 2 66 90 98 85 56 72 5 2 8 M4 0 8 1 25 mm2 min 3G3AX DL2004 0 4 66 90 98 95 56 72 5 2 8 M4 1 0 1 25 mm2 min 3G3AX DL2007 0 75 66 90 9...

Page 216: ...100 138 110 95 80 7 11 M4 3 6 3 5 mm2 min 3G3AX DL4075 7 5 111 100 138 115 95 80 7 11 M4 3 9 3 5 mm2 min Inverter input power supply Model Figure No Applicable Inverter capacity kw Dimensions mm Bmax...

Page 217: ...4 1 4 0 4 1 4 1 4 1 4 1 4 0 75 1 4 1 4 1 4 1 4 1 5 1 4 1 4 1 4 1 4 2 2 1 4 1 4 1 4 1 4 3 7 1 4 1 4 1 4 1 4 5 5 1 4 1 4 1 4 1 4 7 5 1 4 1 4 1 4 1 4 Applicable Inverter capacity kw 200 V class 400 V cla...

Page 218: ...3G3AX NFI43 Inverter side 66 52 10 L3 L2 L1 L3 L2 L1 84 100 117 2 5 0 10 M4 67MAX 15 Power supply side Model Dimensions Unit mm A B C D 3G3AX NFI23 128 118 56 10 3G3AX NFI24 144 130 56 11 3G3AX NFI41...

Page 219: ...NFI23 2 2 3 7 3 20 A 6 1 5 250 V 3G3AX NFI24 5 5 3 30 A 9 1 5 250 V 3G3AX NFI25 7 5 3 40 A 12 1 5 250 V 3 phase 480 V 10 Max 3G3AX NFI41 0 4 to 2 2 3 7 A 2 7 5 250 V 3G3AX NFI42 3 7 3 10 A 4 7 5 250 V...

Page 220: ...7 23 7 5 Options 7 Specifications EMC compatible Noise Filter Dimensional Drawing 3G3AX EFIB1 EFI21 4 5 L3 T S R L1 L2 10 18 44 57 110 205 190 176 6 7 5 7 5 40 66 80 2 M4 6 5 6 5 67...

Page 221: ...cifications 3G3AX EFIB2 EFI22 3G3AX EFIB3 EFI23 L1 T S R L2 L3 N 66 10 18 44 57 118 110 205 176 6 190 7 5 7 5 40 110 98 8 M4 6 6 4 5 67 L3 T S R L1 L2 10 18 57 168 118 44 255 45 240 7 5 7 5 226 6 66 4...

Page 222: ...7 25 7 5 Options 7 Specifications 3G3AX EFI24 66 140 7 M4 18 44 57 168 118 255 240 226 6 7 5 7 5 45 10 128 98 6 6 4 5 L3 T S R L1 L2...

Page 223: ...7 26 7 5 Options 7 Specifications 3G3AX EFI25 L3 T S R L1 L2 10 2 260 MIN 205 235 308 5 331 355 160 40 60 164 182...

Page 224: ...7 27 7 5 Options 7 Specifications 3G3AX EFI41 EFI42 3G3AX EFI43 EFI44 EFI45 74 56 144 73 15 130 5 95 5 M4 11 95 155 165 16 65 95 90...

Page 225: ...3 7 3 10 A 150 mA 7 5 3G3AX EFI43 2 2 3 7 5 5 7 5 3 20 A 170 mA 7 5 3G3AX EFI44 5 5 3 30 A 170 mA 7 5 3G3AX EFI45 7 5 3 40 A 170 mA 7 5 Model Case enclosure rating Input terminal size Input power sup...

Page 226: ...s Power supply Model Rated current A Applicable motor kW External dimensions Height Width Depth mm Weight kg 200 V class 400 V class 3 phase 3 wire rated voltage 500 V AC 3G3AX NFO01 6 0 75 max 2 2 ma...

Page 227: ...imensional Drawing 3G3AX AL2025 AL2055 3G3AX AL2110 3G3AX AL4025 AL4055 AL4110 Ro So To R S T H max H1 max X Y C max D max E max A max R So S To T Ro A max D max E max X Y C max H max H1 max Ro So To...

Page 228: ...140 98 60 40 150 92 50 75 4 0 3G3AX AL2110 5 5 7 5 160 103 70 55 170 106 60 80 5 0 3 phase 400 V AC 3G3AX AL4025 0 4 to 1 5 130 82 60 40 150 92 50 67 2 7 3G3AX AL4055 2 2 3 7 130 98 60 40 150 92 50 75...

Page 229: ...7 32 7 5 Options 7 Specifications Digital Operator 3G3AX OP01 External dimensions Height 55 mm Width 70 mm Depth 10 mm Data display Operation keys RUN command LED indicator FREQ adjuster AX OP01...

Page 230: ......

Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...

Page 232: ...nction output monitor Example Terminal P1 P2 ON Terminal MA OFF d007 Output frequency monitor after conversion 0 00 to 99 99 100 0 to 999 9 1000 to 9999 1000 to 3996 10000 to 39960 Output frequency Co...

Page 233: ...0 Yes s F003 Deceleration time 1 0 01 to 99 99 100 0 to 999 9 1000 to 3000 10 0 Yes s F203 2nd deceleration time 1 0 01 to 99 99 100 0 to 999 9 1000 to 3000 10 0 Yes s F004 Operator rotation directio...

Page 234: ...ency 30 to Max frequency A004 60 No Hz A203 2nd base frequency 30 to Max frequency A204 60 A004 Maximum frequency 30 to 400 60 No Hz A204 2nd maximum frequency 60 Analog input A005 FV FI selection 00...

Page 235: ...ep speed reference 7 0 0 A028 Multi step speed reference 8 0 0 A029 Multi step speed reference 9 0 0 A030 Multi step speed reference 10 0 0 A031 Multi step speed reference 11 0 0 A032 Multi step speed...

Page 236: ...ntrol iSLV 02 No A244 2nd V f characteristics selection 00 A045 Output voltage gain 20 to 100 100 Yes A245 2nd output voltage gain 100 A046 Automatic torque boost voltage compensation gain 0 to 255 10...

Page 237: ...Hz A261 2nd frequency upper limit 0 0 Frequency lower limit to 2nd Max frequency 0 0 A062 Frequency lower limit 0 0 Starting frequency to Frequency upper limit 0 0 No Hz A262 2nd frequency lower limit...

Page 238: ...nction 00 OFF Deviation Target value Feedback value 01 ON Deviation Feedback value Target value 00 No A078 PID output limit function 0 00 to 100 0 0 0 No AVR A081 AVR selection 00 Always ON 01 Always...

Page 239: ...tep acceleration frequency 0 0 A096 2 step deceleration frequency 0 0 to 400 0 0 0 No Hz A296 2nd 2 step deceleration frequency 0 0 A097 Acceleration pattern selection 00 Line 01 S shape curve 00 No A...

Page 240: ...o Hz A153 VR start ratio 0 to 100 0 No A154 VR end ratio 0 to 100 100 No A155 VR start selection 00 Use start frequency A151 01 0 Hz start 01 No Restart after momentary power interruption b001 Retry s...

Page 241: ...0 1 0 No s b223 2nd overload limit parameter 1 0 b028 Overload limit source selection 00 b022 b222 set values 01 Input terminal FV 00 No b228 2nd overload limit source selection 00 Lock b031 Soft lock...

Page 242: ...Regenerative braking function operation selection 00 Disabled 01 Enable Disable during stop 02 Enable Enable during stop 0 0 No b096 Regenerative braking function ON level 200 V class 330 to 380 400...

Page 243: ...T special setting 255 No function 00 No C201 2ndmulti function input 1 selection 00 C002 Multi function input 2 selection 01 C202 2ndmulti function input 2 selection 01 C003 Multi function input 3 sel...

Page 244: ...ection 00 NO contact at MA NC contact at MB 01 NC contact at MA NO contact at MB 00 No C032 Multi function output terminal P2 contact selection 00 C036 Relay output MA MB contact selection 01 Level ou...

Page 245: ...p 02 Ignore 03 Free run 04 Deceleration stop 02 No C077 Communication error timeout 0 00 to 99 99 0 00 No s C078 Communication wait time 0 to 1000 0 No ms Various adjustment C081 FV adjustment 0 0 to...

Page 246: ...detected 07 FBV PID FB value fault 08 NDc network error 10 ODC communication option disconnected 00 No C142 Logic operation function B input 01 No C143 Logic operator selection 00 AND 01 OR 02 XOR 00...

Page 247: ...4 6 8 4 No Pole H204 2nd motor pole number selection 4 H006 Stabilization parameter 0 to 255 100 Yes H206 2nd stabilization parameter 100 H007 Motor voltage selection 00 200 V 01 400 V Factory default...

Page 248: ...peratures should normally be replaced once every 5 years However if the ambient temperature is high or the Inverter is used with its rated current exceeded for example under overload conditions its li...

Page 249: ...INDEX...

Page 250: ...4 58 forced operator function 4 51 forced terminal block 4 52 free run stop FRS selection and stop selection 4 35 frequency addition ADD 4 51 frequency arrival signal 4 54 frequency conversion coeffic...

Page 251: ...function 4 37 relation between torque boost and V f characteristics 4 11 relay output terminal 4 53 reset 4 48 retry selection 4 25 rotation RUN direction monitor 4 1 rotation RUN direction selection...

Page 252: ......

Page 253: ...ddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 OMRON ELECTRONICS LLC One Commerce Drive Schaumburg IL 60173 5302 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 OMRON ASIA PACIFIC PTE LTD No...

Page 254: ...Authorized Distributor Cat No I559 E1 01 Note Specifications subject to change without notice Printed in Japan This manual is printed on 100 recycled paper...

Reviews: