![background image](http://html1.mh-extra.com/html/omron/q2a-a-series/q2a-a-series_installation-and-operation-instructions_742790015.webp)
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions
15
Table 1.3 Wire Gauges
Terminal
Bare Wire
Crimp Ferrule
Recommended Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
Recommended Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
DI1-DI8, DIC, D0V, D24V
H1, H2, HC
PI, +10V, -10V, AI1, AI2, AI3, A0V
PO, AO1, AO2, A0V
RS485+, RS485-, A0V
1NO, 1NC, 1CM, 2NO, 2CM, 3NO, 3CM, 4NO,
4CM
E24V, GND
0.75
(18)
•
Stranded wire
0.2 to 1.0
(24 to 18)
•
Solid wire
0.2 to 1.5
(24 to 16)
0.5
(20)
0.25 to 0.5
(24 to 20)
Crimp Ferrules
Attach an insulated sleeve to the wire when connecting crimp ferrules. We recommend the CRIMPFOX 6
crimping tool from PHOENIX CONTACT.
Figure 1.3 Crimp Ferrule Dimensions
Table 1.4 Crimp Ferrule Models and Dimensions
Wire Gauge
mm
2
(AWG)
Model
L (mm)
L1 (mm)
d1 (mm)
d2 (mm)
0.25 (24)
AI 0.25-8YE
12.5
8
0.8
2.0
0.34 (22)
AI 0.34-8TQ
12.5
8
0.8
2.0
0.5 (20)
AI 0.5-8WH,
AI 0.5-8OG
14
8
1.1
2.5
◆
Drive Start-Up
■
Setup Wizard
Refer to the motor nameplate and record the information in this table before you start the drive.
Item
Value
Motor Rated Power
kW
Motor Rated Voltage
V
Motor Rated Current
A
Motor Rated Frequency
Hz
Item
Value
Motor Maximum Frequency
Hz
Number of Motor Poles
Motor Base Rotation Speed
min
-1
(r/min)
Number of Motor Encoder Pulses
ppr
Open the clock battery cover to put in a battery to use the clock functions. Select a type CR2016 battery with a
nominal voltage of 3 V.
◆
Drive Parameters
Refer to the following table when setting the most important parameters.
Note:
You can change parameters with
“
RUN
”
in the
“
No.
”
column during Run.
No.
(Hex.)
Name
Description
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
0: English, 1: Japanese, 2: German, 3: French, 4: Italian, 5: Spanish, 6: Portuguese, 7: Chinese, 8: Czech, 9: Russian,
10: Turkish, 11: Polish, 12: Greek
A1-03
(0103)
Init Parameters
Sets parameters to default values.
0: No Initialization, 1110: User / Solution Initialization, 2220: 2-Wire Initialization, 3330: 3-Wire Initialization,
4440: Q2pack Init
EN
Summary of Contents for Q2A-A Series
Page 140: ...6 Attachments 140 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 141: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 141 EN...
Page 142: ...6 Attachments 142 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 143: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 143 EN...
Page 144: ...6 Attachments 144 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 145: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 145 EN...