16
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions
No.
(Hex.)
Name
Description
b1-01
(0180)
Freq. Ref. Sel. 1
Sets the input method for the frequency reference.
0: Keypad, 1: Analog Input, 2: Modbus, 3: Option PCB, 4: Pulse Train Input
b1-02
(0181)
Run Comm. Sel 1
Sets the input method for the Run command.
0: Keypad, 1: Analog Input, 2: Modbus, 3: Option PCB
b1-03
(0182)
Stopping Method Selection
Sets the method to stop the motor after removing a Run command or entering a Stop command.
0: Ramp->Stop, 1: Coast->Stop, 2: DC Inj->Stop, 3: Timed Coast->Stop, 9: Distance Stop
b1-04
(0183)
Reverse Operation Selection
Sets the reverse operation function. Disable reverse operation in fan or pump applications where reverse rotation is
dangerous.
0: Enabled, 1: Disabled
C1-01
(0200)
RUN
Accel Time 1
Sets the length of time to accelerate from zero to maximum output frequency.
C1-02
(0201)
RUN
Decel Time 1
Sets the length of time to decelerate from maximum output frequency to zero.
C2-01
(020B)
Jerk@Start of Accel
Sets the jerk acceleration time at start.
C2-02
(020C)
Jerk@End of Accel
Sets the jerk acceleration time at completion.
C2-03
(020D)
Jerk@Start of Decel
Sets the jerk deceleration time at start.
C2-04
(020E)
Jerk@End of Decel
Sets the jerk deceleration time at completion.
C6-01
(0223)
ND/HD Duty Selection
Sets the drive duty rating.
0: HD Rating, 1: ND Rating
C6-02
(0224)
Carrier Frequency Selection
Sets the carrier frequency for the transistors in the drive.
1: 2.0 kHz, 2: 5.0 kHz (4.0 kHz for AOLV/PM), 3: 8.0 kHz (6.0 kHz for AOLV/PM),
4: 10.0 kHz (8.0 kHz for AOLV/PM), 5: 12.5 kHz (10.0 kHz for AOLV/PM), 6: 15.0 kHz (12.0 kHz AOLV/PM),
7: Swing PWM 1 (Audible Sound 1), 8: Swing PWM 2 (Audible Sound 2), 9: Swing PWM 3 (Audible Sound 3),
A: Swing PWM 4 (Audible Sound 4), F: User (C6-03 to C6-05)
d1-01 to d1-16
(0280 - 0291)
RUN
Reference 1 to Reference 16
Sets the frequency reference in the units from
o1-03 [FrqDisplay Unit Selection]
.
d1-17
(0292)
RUN
Jog Reference
Sets the JOG frequency reference in the units from
o1-03 [FrqDisplay Unit Selection]
. Set
H1-xx: MFDI Function
Select = 6 [Jog Reference]
to use the Jog frequency reference.
d2-01
(0289)
FRef Upper Limit
Sets maximum limit for all frequency references. This value is a percentage of
E1-04 [Max Output Frequency]
.
d2-02
(028A)
FRef Lower Limit
Sets minimum limit for all frequency references. This value is a percentage of
E1-04 [Max Output Frequency]
.
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
E1-04
(0303)
Max Output Frequency
Sets the maximum output frequency for the V/f pattern.
E1-05
(0304)
Max Output Voltage
Sets the maximum output voltage for the V/f pattern.
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
E1-09
(0308)
Min Output Frequency
Sets the minimum output frequency for the V/f pattern.
E2-01
(030E)
Mot Rated Current (FLA)
Sets the motor rated current in amps.
E2-11
(0318)
Motor Rated Power (kW)
Sets the motor rated output in 0.01 kW increments.
H1-01 - H1-08
(0438, 0439, 0400 -
0405)
DI1 Function Selection to DI8
Function Selection
Sets the functions for MFDI terminals DI1 to DI8.
H2-01
(040B)
Multi-Function Digital Output 1
Sets the function for MFDO terminal 2NO-2CM.
H2-02
(040C)
Multi-Function Digital Output 2
Sets the function for MFDO terminal 3NO-3CM.
Summary of Contents for Q2A-A Series
Page 140: ...6 Attachments 140 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 141: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 141 EN...
Page 142: ...6 Attachments 142 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 143: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 143 EN...
Page 144: ...6 Attachments 144 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 145: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 145 EN...