138
TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions
Model
Terminals
Recommended Gauge
Applicable Gauge
Wire Stripping
Length
Terminal
Screw
Tightening Torque
IP20
mm
2
(AWG kcmil)
mm
2
(AWG kcmil)
mm
N
∙
m (lb.
∙
in.)
4296
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
70 × 2P
(3/0 × 2P)
70 - 95 × 2P
(2/0 - 4/0 × 2P)
-
M10
20
(177)
-, +1
95 × 2P
(4/0 × 2P)
120 × 2P
(4/0 - 250 × 2P)
-
M10
20
(177)
+3
70 × 2P
(1/0 × 2P)
70 × 2P
(1/0 × 2P)
-
M10
20
(177)
95
(2)
95 - 240
(2 - 350)
-
M10
18 - 23
(159 - 204)
4371
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
120 × 2P
(250 × 2P)
150 × 2P
(250 - 300 × 2P)
-
M12
35
(310)
-, +1
120 × 2P
(250 × 2P)
185 × 2P
(300 - 400 × 2P)
-
M12
35
(310)
+3
70 × 2P
(3/0 × 2P)
50 - 95 × 2P
(1 - 4/0 × 2P)
-
M12
35
(310)
120
(1)
120 - 240
(1 - 350)
-
M12
32 - 40
(283 - 354)
4389
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
120 × 2P
(300 × 2P)
150 × 2P
(250 - 300 × 2P)
-
M12
35
(310)
-, +1
120 × 2P
(400 × 2P)
185 × 2P
(300 - 400 × 2P)
-
M12
35
(310)
+3
95 × 2P
(4/0 × 2P)
50 - 95 × 2P
(1 - 4/0 × 2P)
-
M12
35
(310)
95
(1)
35 - 240
(1 - 350 × 2P)
-
M12
32 - 40
(283 - 354)
4453
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
120 × 4P
(250 × 4P)
150 × 4P
(250 - 300 × 4P)
-
M12
35
(310)
U/T1, V/T2, W/T3
95 × 4P
(4/0 × 4P)
120 - 150 × 4P
(250 - 300 × 4P)
-
M12
35
(310)
-, +1
95 × 4P
(4/0 × 4P)
185 × 4P
(300 - 400 × 4P)
-
M12
35
(310)
+3
70 × 4P
(3/0 × 4P)
95 × 4P
(4/0 × 4P)
-
M12
35
(310)
150
(1/0)
50 - 150
(1/0 - 300)
-
M12
32 - 40
(283 - 354)
4568
4675
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
120 × 4P
(250 × 4P)
150 × 4P
(250 - 300 × 4P)
-
M12
35
(310)
U/T1, V/T2, W/T3
95 × 4P
(4/0 × 4P)
120 - 150 × 4P
(250 - 300 × 4P)
-
M12
35
(310)
-, +1
95 × 4P
(300 × 4P)
185 × 4P
(300 - 300 × 4P)
-
M12
35
(310)
+3
70 × 4P
(3/0 × 4P)
95 × 4P
(4/0 × 4P)
-
M12
35
(310)
95 × 2P
(2/0)
60 - 150
(2/0 - 300)
-
M12
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges. If your installation does not need IP20 protection, smaller
cables can be used.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than 30 mm
2
, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lb.∙in. to 40 lb.∙in.).
*4
Install an RCM/RCD with this wire gauge to maintain compliance with IEC/EN 61800-5-1:2007.
*5
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*6
A junction terminal is necessary to connect a braking resistor unit (LKEB-series) to terminals B1 and B2.
Summary of Contents for Q2A-A Series
Page 140: ...6 Attachments 140 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 141: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 141 EN...
Page 142: ...6 Attachments 142 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 143: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 143 EN...
Page 144: ...6 Attachments 144 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 145: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 145 EN...