TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions
Model
Recommended Gauge (AWG, kcmil)
Terminal
Screw Size
Crimp
Terminal
Model
Crimping Tool
Insulation
Cap Model
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
-, +1
+3
Tool Model
Die Jaw
4296
-
-
-
-
2
M10
R38-10
YF-1
YET-150-1
TD-224, TD-
212
TP-038
-
-
-
1/0 × 2P
-
R60-10
TD-225, TD-
213
TP-060
3/0 × 2P
3/0 × 2P
-
-
-
80-10
TD-227, TD-
214
TP-080
-
-
4/0 × 2P
-
-
R100-10
TD-228, TD-
214
TP-100
4371
-
-
-
-
1
M12
R60-12
YF-1
YET-300-1
TD-321, TD-
311
TP-060
-
-
-
3/0 × 2P
-
80-12
TD-323, TD-
312
TP-080
250 × 2P
250 × 2P
-
-
-
R150-12
TD-325, TD-
313
TP-150
-
-
350 × 2P
-
-
R200-12
TD-327, TD-
314
TP-200
4389
-
-
-
-
1
M12
R60-12
YF-1
YET-300-1
TD-321, TD-
311
TP-060
-
-
-
4/0 × 2P
-
R100-12
TD-324, TD-
312
TP-100
300 × 2P
300 × 2P
-
-
-
R150-12
TD-325, TD-
313
TP-150
-
-
400 × 2P
-
-
R200-12
TD-327, TD-
314
TP-200
4453
-
-
-
-
1/0
M12
R60-12
YF-1
YET-300-1
TD-321, TD-
311
TP-060
-
-
-
3/0 × 4P
-
80-12
TD-323, TD-
312
TP-080
-
4/0 × 4P
4/0 × 4P
-
-
R100-12
TD-324, TD-
312
TP-100
250 × 4P
-
-
-
-
R150-12
TD-325, TD-
313
TP-150
4568
-
-
-
-
2/0
M12
80-12
YF-1
YET-300-1
TD-323, TD-
312
TP-080
3/0 × 4P
-
-
4/0 × 4P
-
-
-
R100-12
TD-324, TD-
312
TP-100
250 × 4P
-
-
-
-
R150-12
TD-325, TD-
313
TP-150
-
300 × 4P
4675
-
-
-
-
2/0
M12
80-12
YF-1
YET-300-1
TD-323, TD-
312
TP-080
-
-
-
4/0 × 4P
-
R100-12
TD-324, TD-
312
TP-100
300 × 4P
300 × 4P
-
-
-
R150-12
TD-325, TD-
313
TP-150
-
-
400 × 4P
-
-
R200-12
TD-327, TD-
314
TP-200
■
Factory-Recommended Branch Circuit Protection for UL Listing
Use branch circuit protection to protect against short circuits and to maintain compliance with UL61800-5-1. We
recommend connecting semiconductor protection fuses on the input side for branch circuit protection. Refer to
Factory Recommended Branch Circuit Protection on page 131
for the recommended fuses.
WARNING
Electrical Shock Hazard. Do not immediately energize the drive or operate peripheral devices after the drive
blows a fuse or trips an RCM/RCD. Wait for the time specified on the warning label at a minimum and make sure that all
indicators are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. Contact the
manufacturer before energizing the drive or peripheral devices if the cause is not known. Failure to obey can cause death or
serious injury and damage to the drive.
•
200 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS symmetrical amperes and 240 Vac when there is a short circuit in the power supply.
•
400 V class
Summary of Contents for Q2A-A Series
Page 140: ...6 Attachments 140 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 141: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 141 EN...
Page 142: ...6 Attachments 142 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 143: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 143 EN...
Page 144: ...6 Attachments 144 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Page 145: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 145 EN...