Appendix 1 Specifications
A-10
Item Specification
Communications func-
tions
Data links and message service
Number of data link
words
•
Transmission area per node:
1,000 words max. (2,000 bytes)
•
Send/receive data link areas per SYSMAC CS-series PLC:
12,000 words max. (24,000 bytes)
•
Send/receive data link areas per SYSMAC C200HX/HG/HE, CVM1, or
CV-series PLC:
8,000 words max. (16,000 bytes)
•
Send/receive data link areas per personal computer:
32,000 words max. (64,000 bytes)
•
Total send data link words on entire network:
32,000 words max. (64,000 bytes)
Data link areas
Bit (CIO, and LR Area), data memory (DM Area), expansion data memory (EM
Area)
Message length
2,012 bytes max.
RAS functions
•
Polling unit backup function
•
Self-diagnosis (hardware check at startup)
•
Internode tests and broadcast test (via FINS commands)
•
Watchdog timer
•
Error log
Error correction
Manchester code check
CRC check (CCITT X
16
+X
12
+X
5
+1)
Note: A Controller Link Interface Unit can be used only for the NS15, NS12, and NS10 NS-
series PTs.
•
Video Input Specifications
Item Specifications
Input system
NTSC (RS-170A compliant) or PAL
Scanning system (See note.)
Interlaced
Input signal
1.0 V p-p 75
Ω
Signal input connector
BNC connector
Note: The NS-series PTs do not support progressive scanning (i.e., non-interlaced scanning)
Item Specifications
Model NS-CA001
NS-CA002
Dimensions
150 x 90 x 21 mm (WxHxD)
150 x 102 x 22 mm (WxHxD)
Weight
0.5 kg or less
Ambient operating
temperature
•
NS12-V1/-V2 and NS10-V1/-V2
Mounting angle of 0
°
or greater but
less than 30
°
to horizontal: 0 to
35
°
C
Mounting angle of 30
°
or greater
but less than 90
°
to horizontal: 0 to
50
°
C
•
NS8-V1/-V2
Mounting angle of 0
°
or greater but
less than 30
°
to horizontal: 0 to
35
°
C
Mounting angle of 30
°
min. but less
than 90
°
to horizontal plane: 0 to
45
°
C
Mounting angle of 90
°
to horizon-
tal: 0 to 50
°
C
•
NS12-V1/-V2, NS10-V1/-V2,
and NS8-V1/-V2
Mounting angle of 0
°
or
greater but less than 30
°
to
horizontal: 0 to 35
°
C
Mounting angle of 30
°
or
greater but less than 90
°
to
horizontal: 0 to 45
°
C
Mounting angle of 90
°
to hori-
zontal: 0 to 50
°
C
Ambient storage
temperature
−
20 to 60
°
C
Summary of Contents for NS15-V2 Series
Page 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Page 2: ......
Page 34: ...1 4 Procedure for Running NS series PTs 1 12...
Page 54: ...2 2 Part Names and Functions 2 20...
Page 144: ...4 4 Recommended Connector Cables 4 28...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Page 246: ...6 11 Verifying Tags 6 72...
Page 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Page 333: ......
Page 334: ......