4-3 High-speed 1:N NT Link
4-22
Using a Programming Console (CJ1 CPU Units Only)
If the PT is connected to the Host Link port (RS-232C port), connect the Programming Con-
sole to the CPU Unit and set the following values at the specified addresses of the PLC
Setup.
PLC
Setup
address
Setting to write
Description
160
8200 hex
Specifies using the Host Link port in 1:N NT Link Mode.
161
000A hex
Baud rate: High-speed (115,200 bps)
166
000
@
hex
If only one PT is connected to the port and it has a unit
number of 0, replace the box at the left with 1. Otherwise,
replace the box with the highest unit number of all the PTs
that are connected.
Reference
If the PT is connected to the peripheral port of the CPU Unit, make the above settings in
words 144, 145, and 150 of the PLC Setup instead of 160, 161, 166.
Setting the Front Panel Switches
•
Using RS-232C
Set DIP switch pin 4 or 5 of the CPU Unit according to the port to which the PT is connected,
as shown below. (The following figure shows a CJ1G CPU Unit. The arrangement depends
on the CPU Unit, but the DIP switch settings are the same.)
DIP switch (inside battery compartment)
Turn ON pin 4 when connecting the PT to
the peripheral port (to use the communications
settings in the PLC Setup).
Turn OFF pin 5 when connecting the PT to
the RS-232C port (to use the communications
settings in the PLC Setup).
Peripheral port
Connected to a Programming
Console or other device.
RS-232C port
Connected to a Programming Console or other
device.
Summary of Contents for NS15-V2 Series
Page 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Page 2: ......
Page 34: ...1 4 Procedure for Running NS series PTs 1 12...
Page 54: ...2 2 Part Names and Functions 2 20...
Page 144: ...4 4 Recommended Connector Cables 4 28...
Page 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Page 246: ...6 11 Verifying Tags 6 72...
Page 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Page 333: ......
Page 334: ......